Table ED-2 20-130 Tons Electrical Service Sizing Data — Motors
Nominal Voltage
200 230 460 575
FLA FLA FLA FLA
Nominal Tons Condenser Fan Motors
20 8.2 8.2 3.6 2.8
25 12.3 12.3 5.4 4.2
30 12.3 12.3 5.4 4.2
40 16.4 16.4 7.2 5.6
50 24.6 24.6 10.8 8.4
55 24.6 24.6 10.8 8.4
60 24.6 24.6 10.8 8.4
70 24.6 24.6 10.8 8.4
75 24.6 24.6 10.8 8.4
90 32.8 32.8 14.4 11.2
105 41.0 41.0 18.0 14.0
115 41.0 41.0 18.0 14.0
130 49.2 49.2 21.6 16.8
Motor Horsepower Supply Fan Motors
3 11.2 8.8 4.4 3.8
5 15.2 13.4 6.6 5.3
7
1
/
2
22.3 19.6 9.8 7.8
10 29.7 26.4 13.2 10.3
15 44.4 38.6 19.3 15.4
20 58.7 51.0 25.5 20.4
25 70.5 61.0 30.5 24.5
30 86.5 75.0 37.5 30.0
40 112.0 97.0 48.5 39.0
Motor Hp Exhaust Fan Motor
1
1
/
2
5.0 4.4 2.2 1.8
3 11.2 8.8 4.4 3.8
5 15.2 13.4 6.6 5.3
7
1
/
2
22.3 19.6 9.8 7.8
10 29.7 26.4 13.2 10.3
15 44.4 38.6 19.3 15.4
20 58.7 51.0 25.5 20.4
25 70.5 61.0 30.5 24.5
30 86.5 75.0 37.5 30.0
40 112.0 97.0 48.5 39.0
Table ED-3 20-130 Tons Electrical Service Sizing Data Electric Heat
Module (Electric Heat Units Only)
Voltage
200 230 460 575
Module KW FLA FLA FLA FLA
30 83.3 72.2 36.1 28.9
50 138.8 120.3 60.1 48.1
70 194.3 168.4 84.2 67.4
90 249.8 216.5 108.3 86.6
110 305.3 264.6 132.3 105.9
130 156.4 125.1
150 180.4 144.3
170 204.5 163.6
190 228.5 182.8
Note: Electric heat FLA are determined at 208, 240, 480 and 600 volts.
Table ED-6 Voltage Utilization Range
Voltage
Unit Voltage Utilization Range
200/60/3 180-220
230/60/3 207-253
380/50/3 342-418
415/50/3 373-457
460/60/3 414-506
575/60/3 517-633
Table ED-4 20-130 Tons Electrical Service
Sizing Data Control Power Transformer
Heating and Cooling Modes
Nominal Tons (Add) FLA
20-40 3
50-75 6
90-130 8
Electrical
Data
Nominal Tons (Add) FLA
20-30 1
40-60 2
70-105 3
115-130 4
Table ED-5 20-130 Tons Electrical Service
Sizing Data Crankcase Heaters (Heating
Mode on 460/575 Volt Only)