Trane RT-PRC010-EN Air Conditioner User Manual


 
RT-PRC010-EN42
Table PD-29— 90 To 130-Ton Electric Heat Air Temperature Rise
KW Total Cfm
Input MBh 24000 27000 30000 33000 36000 40000
190 648.3 24.9 22.1 19.9 18.1 16.5 15.3
Notes:
1. Air Temperature = kw x 3413 ÷ (scfm x 1.085)
2. Only available in 460/60/3 and 575/60/3 voltages.
Table PD-30— Electric Heat KW Ranges
Nominal Voltage
Nominal
Tons 200 230 460 575
20 30-90 30-110 30-110 30-110
25 30-90 30-110 30-130 30-130
30 30-110 30-110 30-150 30-150
40 50-110 50-110 50-170 50-170
50 70-110 70-110 70-190 70-190
55 70-110 70-110 70-190 70-190
60 90-110 90-110 90-190 90-190
70 90-110 90-110 90-190 90-190
75 90-110 90-110 90-190 90-190
90 NA NA 190 190
105 NA NA 190 190
115 NA NA 190 190
130 NA NA 190 190
Table PD-28 — 20 to 75-Tons Electric Heat Air Temperature Rise
KW Total Cfm
Input MBh 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000
30 102.4 23.6 15.7 11.8 9.4 7.9 6.7 5.9 5.2 4.7 4.3 3.9 3.6
50 170.6 39.3 26.2 19.7 15.7 13.1 11.2 9.8 8.7 7.9 7.1 6.6 6.0
70 238.8 55.0 36.7 27.5 22.0 18.3 15.7 13.8 12.2 11.0 10.0 9.2 8.5
90 307.1 47.2 35.4 28.3 23.6 20.2 17.7 15.7 14.2 12.9 11.8 10.9
110 375.3 57.7 43.2 34.6 28.8 24.7 21.6 19.2 17.3 15.7 14.4 13.3
130 443.6 51.1 40.9 34.1 29.2 25.6 22.7 20.4 18.6 17.0 15.7
150 511.8 59.0 47.2 39.3 33.7 29.5 26.2 23.6 21.4 19.7 18.1
170 580.1 53.5 44.6 38.2 33.4 29.7 26.7 24.3 22.3 20.6
190 648.3 59.8 49.8 42.7 37.3 33.2 29.9 27.2 24.9 23.0
Notes:
1. Maximum permitted air temperature rise; 20-30 tons (UL — 50 F) (CSA — 60 F), 40 — 60 ton (UL/CSA — 50 F).
2. Air temperature rise = kw x 3413 ÷ (scfm x 1.085)
3. All heaters on units provide 3 increments of capacity.
4. 200 and 230 volt electric heat rooftops require dual power supplies to the control box. All other rooftops have single power connections. See Electrical Data Section for
electrical sizing information.