Schneider Electric iEM3200 Indoor Furnishings User Manual


 
98 DOCA0005EN-04
Specifications iEM3100 / iEM3200 / iEM3300 series user manual
Power system inputs: iEM32•• meters
Inputs and outputs
Characteristic Value
Voltage inputs
Measured voltage
Wye: 100 - 277 V L-N, 173 - 480 V L-L ±20%
Delta: 173 - 480 V L-L ±20%
Overload 332 V L-N or 575 V L-L
Impedance 3 M
Frequency 50 / 60 Hz ±10%
Measurement category III
Minimum wire temperature rating required 90 °C (194 °F)
Maximum device consumption < 10 VA
Wire 2.5 mm
2
/ 14 AWG
Wire strip length 8 mm / 0.31 in
Torque 0.5 Nm / 4.4 in•lb
Current inputs
Nominal current 1 A or 5 A
Measured current 20 mA to 6 A
Withstand 10 A continuous, 20 A at 10 sec/hr
Minimum wire temperature rating required 90 °C (194 °F)
Impedance < 1 m
Frequency 50 / 60 Hz ±10%
Burden < 0.036 VA at 6 A
Wire 6 mm
2
/ 10 AWG
Wire strip length 8 mm / 0.31 in
Torque 0.8 Nm / 7.0 in•lb
Characteristic Value Meters
Programmable digital
output
Number 1
iEM3135 / iEM3155 / iEM3165 /
iEM3235/ iEM3255 / iEM3265 /
iEM3335 / iEM3355 / iEM3365
Type Form A
Load voltage 5 – 40 V DC
Maximum load current 50 mA
Output resistance 0.1 – 50
Isolation 3.75 kV rms
Wire 1.5 mm
2
/ 16 AWG
Wire strip length 6 mm / 0.23 in
Torque 0.5 Nm / 4.4 in•lb
Pulse output
Number 1
iEM3110 / iEM3210 / iEM3310
Type S0 form (IEC 62053-31 compatible)
Pulses / kWh Configurable
Voltage 5 – 30 V DC
Current 1 – 15 mA
Pulse width
Configurable
Minimum width is 50 ms
Isolation 3.75 kV rms
Wire 2.5 mm
2
/ 14 AWG
Wire strip length 7 mm / 0.28 in
Torque 0.5 Nm / 4.4 in•lb