iEM3100 / iEM3200 / iEM3300 series user manual Front panel display and meter setup
DOCA0005EN-04 39
Related topics
See “Modifying parameters” on page 39 for instructions on using the front panel buttons to
configure list and numeric value settings.
See “Configuration mode menus” on page 40 for a diagram of your device’s configuration screens.
Com. Protection setting
For meters with communications capabilities, you can enable or disable the Com. Protection setting. If
this setting is enabled, you must use the display to configure certain settings (for example, wiring or
frequency, etc.) and perform resets; you cannot use communications.
The protected settings and resets are:
Power system settings (for example, wiring, frequency, CT ratios)
Date and time settings
Multi-tariff settings
Communications settings
Partial energy reset
Modifying parameters
There are two methods for modifying a parameter, depending on the type of parameter:
selecting a value in a list (for example, selecting 1PH2W L-N from a list of available power
systems), or
modifying a numerical value, digit by digit (for example, entering a value for the date, time or VT
primary).
NOTE: Before you modify any parameters, ensure that you are familiar with the HMI functionality and
navigation structure of your device in configuration mode.
Related topics
See “Configuration mode menus” on page 40 for information on navigating the configuration
menus on your device.
Selecting a value from a list
1. Use the down button to scroll through the parameter values until you reach the desired value.
2. Press OK to confirm the new parameter value.
Example: Configuring a list value
To set the nominal frequency of the meter:
1. Enter configuration mode and press the down button until you reach Frequency then press OK to
access the frequency configuration.
2. Press the down button to select the frequency you want then click OK. Press OK again to save
your changes.
Modifying a numerical value
When you modify a numerical value, the digit on the far right side is selected by default (except for
Date/Time).