Schneider Electric iEM3200 Indoor Furnishings User Manual


 
iEM3100 / iEM3200 / iEM3300 series user manual Communications via Modbus RS-485
DOCA0005EN-04 55
Set Pulse Output (iEM3155 / iEM3255 / iEM3355)
Set Tariff (iEM3155 / iEM3255 / iEM3355)
Set Digital Input as Partial Energy Reset (iEM3155 / iEM3255 / iEM3355)
Command
Number
Action
(R/W)
Size Type Unit Range Description
2003
W 1 UInt16 (Reserved)
W 1 UInt16 (Reserved)
W 1 UInt16 0, 1
Pulse Output enable / disable
0 = Disable
1 = Enable
W 2 Float32 pulse/kWh
iEM3155 / iEM3355:
1, 10, 20, 100, 200,
1000
iEM3255: 0.01, 0.1,
1, 10, 100, 500
Pulse constant
W 1 UInt16 (Reserved)
W 1 UInt16 (Reserved)
W 2 Float32 (Reserved)
W 1 UInt16 (Reserved)
W 1 UInt16 (Reserved)
W 2 Float32 (Reserved)
2038
W 1 UInt16 (Reserved)
W 1 UInt16 (Reserved)
W 1 UInt16 ms 50, 100, 200, 300 Pulse width
Command
Number
Action
(R/W)
Size Type Unit Range Description
2060
W 1 UInt16 (Reserved)
W 1 UInt16 0, 1, 2, 4
Multi Tariff Mode
0 = Disable Multi Tariff
1 = Use COM as Tariff Control (maximum 4 tariffs)
2 = Use Digital Input as Tariff Control (2 tariffs)
4 = Use Internal Clock as Tariff Control (maximum 4
tariffs)
2008
W 1 UInt16 (Reserved)
W 1 UInt16 1–4
Tariff
1 = T1
2 = T2
3 = T3
4 = T4
NOTE: You can only set the tariff using this method if the
Tariff Mode is set to by Communication.
Command
Number
Action
(R/W)
Size Type Unit Range Description
6017
W 1 UInt16 (Reserved)
W 1 UInt16 0, 1
Digital Input to Associate:
0 = Disable
1 = Enable