Front panel display and meter setup iEM3100 / iEM3200 / iEM3300 series user manual
Setting the clock initially
The following diagram illustrates how to set the clock when you initially power up the device or after a
power failure. To set the clock during normal operation, see the section on device configuration.
NOTE: Password entry is only required for meters that support a password.
Related topics
See “Device configuration” on page 38 for information on setting the clock during normal device
operation.
Device configuration
The default factory settings are listed in the following table:
Entering configuration mode
1. Press and hold OK and ESC at the same time for about 2 seconds.
2. Enter the meter password, if prompted. The Access Counter screen displays, indicating the
number of times the configuration mode has been accessed.
The front panel display in configuration mode
The diagram below illustrates the various elements of the display in configuration mode:
Date & Time
Set?
Password
0010
OK
OK
Date
01-Jan-2000
OK
Time
00:00
OK
Date & Time
Save Settings?
OKOK
DD-MM-YYYY hh:mm
Total Active E
kWh
1234.5
Menu Factory settings
Wiring
iEM31••: 3PH4W
iEM32••: 3PH4W; 3 CTs on I1, I2, and I3; Direct-No VT
iEM33••: 3PH4W
CT Ratio CT Secondary = 5 A; CT Primary = 5 A
CT & VT Ratio
CT Secondary = 5 A; CT Primary = 5 A
VT Secondary = 100 V; VT Primary = 100 V
Frequency 50 Hz
Date 1-Jan-2000
Time 00:00:00
Multi Tariffs Disable
Overload Alarm Disable
Digital Output Disable
Digital Input Input Status
Pulse Output 100 imp / kWh
Communication Varies depending on protocol
Com.Protection Enable
Contrast 5
Password 0010
A Parameter
B Setting
C Configuration mode icon
D Indicates that the setting impacts the Multi Tariff feature
Config
> 2s
..\In. Pulse Const.
Overriding!
00500