Analog Value object
There is one Analog Value (AV) object available on the meter, named AV00 - Command. The
available commands are listed in the following table. Enter the number in the Present_Value column
in the Present_Value property of the AV object to write the associated command to the meter.
Binary Input objects
The following table lists the Binary Input (BI) objects available on the meter.
NOTE: The Value Type for all BI objects is Boolean.
Command Present_Value entry Object name / description
Acknowledge Overload Alarm 20001.00
Acknowledge an overload alarm.
The alarm indicator disappears from the front panel display after you
acknowledge the alarm; however, this does not address the state that
caused the alarm.
Reset Partial Energy Counter 2020.00
Reset partial energy accumulation to 0.
Partial Active / Reactive Energy, Energy by Tariff and Phase Energy
registers are reset.
Reset Input Metering Counter 2023.00 Resets input metering accumulation to 0.
Object ID Object name / description
0
BI00 - Digital Output Enable
Indicates whether or not the digital output functions as an energy pulse output:
0 = Digital output disabled
1 = Digital output is associated with active energy pulse output
1
BI01 - Digital Input Association Enable
Indicates whether or not the digital input is associated with input metering:
0 = Digital input is not associated with input metering.
1 = Digital input is associated with input metering.
2
BI02 - Digital Input Status
0 = relay open
1 = relay closed
NOTE: This information only applies if the digital input is set to Input Status.
3
BI03 - Alarm Enable
Indicates whether the overload alarm is enabled or disabled:
0 = disabled
1 = enabled
4
BI04 - Digital Output Association Enable
Indicates if the digital output is configured for alarming:
0 = digital output disabled
1 = for Alarm (digital output is associated with the overload alarm)
5
BI05 - Alarm Status
0 = Alarm is inactive
1 = Alarm is active
6
BI06 - Unacknowledged status
0 = historic alarm is acknowledged
1 = historic alarm is unacknowledged