Schneider Electric iEM3100 Indoor Furnishings User Manual


 
80 DOCA0005EN-04
Communications via M-Bus iEM3100 / iEM3200 / iEM3300 series user manual
Instantaneous measurements
NOTE: E denotes the extension bit; the hex value assumes E = 0.
Meter status information
Use the following information to read system and status information from the meter. See the section
regarding telegram information for meter configuration for more information on writing to the meter.
Date and time information
NOTE: E denotes the extension bit; the hex value assumes E = 0.
8780 1003————Rate D (tariff 4) active energy import
07 E110 0001 61 Input metering accumulation
04 ED E000 1100 0C Date and time of last partial energy reset
04 ED E000 1110 0E Date and time of last input metering reset
Data format DIFE Primary VIF
Primary VIFE Manufacturer-specific VIFE
Description
bin hex bin hex
Data format DIFE Primary VIF
Primary VIFE Manufacturer-specific VIFE
Description
bin hex bin hex
05 AE E000 0001 01 Active power Phase 1
05 AE E000 0010 02 Active power Phase 2
05 AE E000 0011 03 Active power Phase 3
052E————Total active power
85402E————Total reactive power
8580 402E————Total apparent power
05 E100 1001 C9 E000 0001 01 Voltage L1-N
05 E100 1001 C9 E000 0010 02 Voltage L2-N
05 E100 1001 C9 E000 0011 03 Voltage L3-N
05 E100 1001 C9 E000 0100 04 Average voltage line-to-neutral
05 E100 1001 C9 E000 0101 05 Voltage L1-L2
05 E100 1001 C9 E000 0110 06 Voltage L2-L3
05 E100 1001 C9 E000 0111 07 Voltage L3-L1
05 E100 1001 C9 E000 1000 08 Average voltage line-to-line
05 E101 1100 DC E000 0001 01 Phase 1 current
05 E101 1100 DC E000 0010 02 Phase 2 current
05 E101 1100 DC E000 0011 03 Phase 3 current
05 E101 1100 DC E000 0000 00 Average current
05 E000 1010 0A Total power factor
05 E000 1011 0B Frequency
Data format Primary VIF
Manufacturer-specific VIFE
Description
bin hex
04 6D Meter date and time (DD/MM/YYYY hh:mm:ss)
06 E010 0000 20 Meter operation timer: the time in seconds since the device was last powered up