iEM3100 / iEM3200 / iEM3300 series user manual Communications via LonWorks
DOCA0005EN-04 71
Echelon LonMaker plug-in for data display and meter configuration
The information in this section assumes that you have an advanced understanding of system
administration using Echelon LonMaker.
The LonMaker plug-in provides a graphical user interface where you can view meter values and
configure meter settings. Once you install and register the plug-in with LonMaker, it opens instead of
the default LonMaker browser when you browse the meter in LonMaker.
To add devices to LonMaker, you need access to the device service pin when commissioning the
device or your need the device Neuron ID recorded in an accessible location.
Related topics
• Refer to http://www.echelon.com/products/tools/integration/lonmaker/ and the LonMaker
documentation for more information on using LonMaker.
• See “Location of the service pin and Neuron ID” on page 64 for the location of the service pin and
Neuron ID.
Installing and registering the LonMaker plug-in
Before you install the plug-in:
• Download the plug-in and XIF file for your device from www.schneider-electric.com or contact your
sales representative to obtain these files.
• Make sure Echelon LonMaker is closed.
1. Navigate to the location where you saved the plug-in. Extract the files if they are in a .zip file.
2. Double-click setup.exe. A welcome screen appears. Click Next.
3. Select the installation folder where you want to install the plug-in. Click Browse if you want to
select a different location. Click Next. A confirmation screen appears.
4. Click Next to begin the installation.
NOTE: If LonMaker is open, a message appears instructing you to close LonMaker and restart the
plug-in installation.
nciAllEnergy SCPTminSendTime
Floating-point energy values:
• nvoTotWhImp
• nvoTotWhExp
• nvoTotVARhImp
• nvoTotVARhExp
• nvoPartialWh
• nvoPartialVARh
• nvoPh1Wh
• nvoPh2Wh
• nvoPh3Wh
• nvoTariffAWh
• nvoTariffBWh
• nvoTariffCWh
• nvoTariffDWh
The minimum interval, in seconds, between consecutive transmissions of the
listed variable values to the network.
No updates to the value of the applicable variables are sent over the network
until the minimum interval has elapsed, regardless of whether or not the value of
the variable has changed.
After an update is sent, the counter is reset to 0.
nciAllPower SCPTminSendTime
• nvoActPowerPh1
• nvoActPowerPh2
• nvoActPowerPh3
• nvoActPowerSum
• nvoRctPowerSum
• nvoAppPowerSum
nciAllVoltage SCPTminSendTime
• nvoVoltsL1N
• nvoVoltsL2N
• nvoVoltsL3N
• nvoVoltsLNAvg
• nvoVoltsL1L2
• nvoVoltsL2L3
• nvoVoltsL3L1
• nvoVoltsLLAvg
nciAllCurrent SCPTminSendTime
• nvoCurrentPh1
• nvoCurrentPh2
• nvoCurrentPh3
• nvoCurrentAvg
nciAllPowerFactor SCPTminSendTime • nvoAvgPwrFactor
nciFrequency SCPTminSendTime • nvoFrequency
nci variable UCPTs/SCPTs Applies to... Description