Schneider Electric iEM3100 Indoor Furnishings User Manual


 
46 DOCA0005EN-04
Front panel display and meter setup iEM3100 / iEM3200 / iEM3300 series user manual
Configuration menus for iEM3250
Multi Tariffs (iEM3215) Control Mode
Disable
by Internal Clock
Select the tariff control mode:
Disable: the Multi Tariff function is disabled.
by Digital Input: the digital input is associated with the multi-tariff
function. A signal to the digital input changes the active tariff.
by Internal Clock: the device clock controls the active tariff. If you set the
Control Mode to by Internal Clock, you must also configure the schedule.
Set the time when each tariff period starts, using the 24 hour clock format
(00:00 to 23:59). The start time of the next tariff is the end time of the
current tariff. For example, T2 start equals the end of T1.
Contrast Contrast 1-9 Increase or decrease the value to increase or decrease the display contrast.
Password
(iEM3210 / iEM3215)
Password 0-9999 Sets the password for accessing the meter configuration screens and resets.
Reset Config Reset Config Settings are reset to their defaults, except for Password. Meter restarts.
Section Parameter Options Description
Wiring
Type
Frequency
Frequency
Date
Date
Time
Time
Contrast
Contrast
Reset Config
Reset Config
Communication
Slave Address
Baud Rate
Parity
Section Parameter Options Description
Wiring Type
3PH4W
1PH2W L-N
1PH2W L-L
1PH3W L-L-N
3PH3W
1PH4W Multi L-N
Select the power system type the meter is wired to.
Frequency Frequency
50
60
Select the frequency of the electrical power system, in Hz.
Date Date DD-MMM-YYYY Set the current date using the specified format.
Time Time hh:mm Set the time using the 24-hour format.
Communication
Slave Address 1 - 247
Set the address for this device. The address must be unique for each device in
a communications loop.
Baud Rate
19200
38400
9600
Select the speed for data transmission. The baud rate must be the same for all
devices in a communications loop.
Parity
Even
Odd
None
Select None if the parity bit is not used. The parity setting must be the same for
all devices in a communications loop.
NOTE: Number of stop bits = 1.
Contrast Contrast 1-9 Increase or decrease the value to increase or decrease the display contrast.
Reset Config Reset Config Settings are reset to their defaults, except for Password. Meter restarts.