Schneider Electric iEM3100 Indoor Furnishings User Manual


 
iEM3100 / iEM3200 / iEM3300 series user manual Communications via M-Bus
DOCA0005EN-04 79
Telegram information for data records
The following sections outline the telegram information used in data records. The tables contain the
following information (if applicable):
Data format in hex (for example, 16-bit integer)
Primary VIF in hex
Primary VIFE codes in bin and hex
Manufacturer-specific VIFE codes in bin and hex
Meter information
NOTE: E denotes the extension bit; the hex value assumes E = 0.
Related topics
See “Troubleshooting” on page 103 for more information on the diagnostics codes.
Energy and energy by tariff measurements
The energy and energy by tariff measurements listed below are preserved through power failures.
NOTE: E denotes the extension bit; the hex value assumes E = 0.
Data format
Primary VIF Extension
Description
bin hex
0D E000 1010 0A
Manufacturer
18-bit ASCII = Schneider Electric
0D E000 1100 0C Model
03 E0001 0111 17
Meter error codes:
0 = Code 101: EEPROM error
1 = Code 102: No calibration table
2 = Code 201: Mismatch between frequency settings and frequency measurements
3 = Code 202: Mismatch between wiring settings and wiring inputs
4 = Code 203: Phase sequence reversed
5 = Code 204: Total active energy negative due to incorrect voltage or current
connections
6 = Code 205: Date and time are reset due to a power failure
7 = Code 206: Pulse missing due to overspeed of energy pulse output
8 = Code 207: Abnormal internal clock function
9 = Internal data bus communications error
Data format DIFE Primary VIF
Primary VIFE Manufacturer-specific VIFE
Description
bin hex bin hex
07 03 Total active energy import
07 83 E000 1001 09 Total active energy export
87 40 03 Total reactive energy import
87 40 83 E000 1001 09 Total reactive energy export
07 83 E000 1101 0D Partial active energy import
87 40 83 E000 1101 0D Partial reactive energy import
07 83 E000 0001 01 Active energy import phase 1
07 83 E000 0010 02 Active energy import phase 2
07 83 E000 0011 03 Active energy import phase 3
03 E001 0000 10
Active tariff
0 = Multi Tariff feature is disabled
1 = rate A (tariff 1) active
2 = rate B (tariff 2) active
3 = rate C (tariff 3) active
4 = rate D (tariff 4) active
87 10 03 Rate A (tariff 1) active energy import
87 20 03 Rate B (tariff 2) active energy import
87 30 03 Rate C (tariff 3) active energy import