Regency P33S-NG4 Indoor Fireplace User Manual


 
Regency P33 Sunrise
TM
Gas Fireplace
22
INSTALLATION
INSTALLATION
16
2
4
6
8
10
12
14
2
0
0
12
20
6
14
30” (762mm)
Minimum
Height
Requirement
4
8
10
18
16
Vertical Height (Feet)
Horizontal (Feet)
8"(0.2m)
2’ (0.6m)
RIGID PIPE VENTING ARRANGEMENTS
Horizontal Terminations
REGENCY
®
DIRECT VENT SYSTEM (FLEX)
(Propane & Natural Gas)
This diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 45
o
and one 90
o
elbow (two 45
o
elbows
equal one 90
o
elbow).
Note: Must use optional rigid pipe adaptor (Part # 510-994) when using rigid pipe vent systems. (Refer "Rigid Pipe Venting Systems"
Section)
Maintain clearances to combustibles.
Horizontal vent must be supported every 3 feet.
Firestops are required at each oor level and whenever passing through a wall.
A vent guard should be used whenever the
termination is lower than the speci ed minimum
or as per local codes.
Note: Regency
®
Direct Vent System (Flex)
is only approved for horizontal
terminations.
Minimum
Simpson Dura-Vent Center-Line
Minimum
Flex Kit Center-Line
2
0
6
4
8
2
0
6
4
8
Vertical Height (Feet)
Min. 26”
(660mm)
Horizontal (Feet)
Max. 24"(0.6m)
2
0
6
4
8
2
0
6
4
8
Vertical Height (Feet)
Min. 30"
(762mm)
Horizontal (Feet)
Max. 24"(0.6m)