Regency P33 Sunrise
TM
Gas Fireplace 15
INSTALLATION
Wherever necessary due to
external location of cap, the
AstroCap can be replaced with
the FPI Riser Vent Termina-
tion Cap.
REGENCY
®
DIRECT VENT FLEX SYSTEM
Horizontal Terminations Only
This venting system, in combination with the P33S-4 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock
Hersey. The location of the termination cap must conform to the requirements in the "Exterior Vent Terminal Locations" Section .
Regency
®
Direct Vent Flex Termination Kit (Part # 946-513) includes all the parts needed to install the P33S-4 with a maximum run of 2
feet. If installing the P33S-4 with a continuous vent length of more than 2 ft (.6m) to a maximum of 10 ft. (3.0m) use Kit # 946-515 (4 ft) or 946-
516 (10 ft) or see "Rigid Pipe Venting Systems" Section for alternate venting arrangements.
MINIMUM
FLEX KIT CENTER-LINE
MINIMUM
RIGID PIPE CENTER-LINE
2
0
6
4
8
2
0
6
4
8
Vertical Height (Feet)
Min. 30"
(762mm)
Horizontal (Feet)
Max. 24"(0.6m)
2
0
6
4
8
2
0
6
4
8
Vertical Height (Feet)
Min. 26”
(660mm)
Horizontal (Feet)
Max. 24"(0.6m)
AstroCap Flex Kits
1
6-7/8" dia. fl exible liner (kit length)
2
4" dia. fl exible liner (kit length)
3
spring spacers (3)
4
thimble (2)
5
AstroCap termination cap (1)
6
screws (12)
7
tube of Mill Pac (1)
8
plated screws (8)
Notes:
1) Liner sections should be continuous
without any joints or seams.
2) Only Flex pipe purchased from Regency
®
may be used for Flex installations.
Alternate
Horizontal
Termination
Caps
INSTALLATION