Regency P33S-NG4 Indoor Fireplace User Manual


 
Regency P33 Sunrise
TM
Gas Fireplace 19
INSTALLATION
Vent must be supported at offsets.
Firestops are required at each oor level and whenever passing through a wall.
Maintain clearances to combustibles.
Note: Must use optional rigid pipe adapter when using rigid vent systems (Part # 510-994).
RIGID PIPE VENTING ARRANGEMENTS
Vertical Terminations
(Propane & Natural Gas)
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using one 90
o
elbow, with
rigid pipe vent systems for Propane and Natural Gas.
Minimum 8'6” (2.6m)
Maximum 35’ (10.6m)
35
8
10
12
14
16
18
20
22
24
26
28
30
6
0
2
4
2
0
6
4
Horizontal (Feet)
Floor
2
0
6 10
4
8
12
Vertical Height (Feet)
Minimum 8'6” (2.6m)
Maximum 27’ (8.2m)
Horizontal (Feet)
Min. 12” (305mm)
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
0
2
4
6
Max. 10’ (3m)
(centerline to centerline)
Floor
INSTALLATION