Regency L676S-NG1 Indoor Fireplace User Manual


 
Regency® L676S Direct Vent Gas Fireplace 17
INSTALLATION
INSTALLATION
VENTING ARRANGEMENTS
HORIZONTAL TERMINATION (FLEX)
Regency
®
Direct Vent System
These venting systems, in combination with the L676S, have been tested and listed as a direct vent system by Warnock Hersey. The location of the
termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the
parts needed to install the L676S using a fl exible vent.
FPI Kit # Length Contains:
#946-615 4 Feet
1) 8” fl exible liner (Kit length)
2) 5” fl exible liner (Kit length)
3) spring spacers
4) thimble
5) AstroCap termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” drill point
10) vinyl siding standoff
#946-618 6 Feet
#946-616 10 Feet
8” dia.
Flue pipe
5” dia. flue pipe
spring spacer
Termination Cap
AstroCap XL
TM
(Part #946-623/P)
Wall Thimble
(Mandatory in all
Horizontal Terminations)
Vinyl Siding
Standoff
Vent Guard - if required*
(Part #946-506/P)
Notes:
1) Liner sections should be continuous without any joints
or seams.
2) Only Flex pipe purchased from FPI may be used for Flex
installations.
3) Horizontal vent must be supported every 3 feet.
4) A wall thimble is mandatory for all horizontal terminations
due to high temperatures.