Regency L234-LP Indoor Fireplace User Manual


 
Regency
®
L234 Direct Vent Gas Insert 13
INSTALLATION
GAS PIPE
PRESSURE TESTING
The appliance must be isolated from the gas supply piping system by closing
its individual manual shut-off valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator built into the gas control,
and should be checked at the pressure test point.
NOTE: To properly check gas pressure, both inlet and manifold
pressures should be checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise
with a 1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16"
ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with the unit burning and
the setting should be within the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn off the gas valve, disconnect
the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not over tighten.
SIT VALVE DESCRIPTION
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Manifold (Outlet) Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point
1
2
3
4
5
6
IN OUT
INSTALLATION