UltraGlow
®
G36D Zero Clearance Direct Vent Gas Fireplace
®
G36D Zero Clearance Direct Vent Gas Fireplace
®
6
INSTALLATION
Diagram 1
This includes:
1)
Clocking the appliance to ensure the correct
fi ring rate (rate noted on label 26,000 Btu/h)
after burning appliance for 15 minutes.
2)
If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
LOCATING YOUR
GAS STOVE
1)
When selecting a location for your fi replace,
ensure that the clearances outlined on this
page are met.
2)
Provide adequate clearances for
servicing.
3)
The appliance must be installed on a fl at,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the fl oor, or raised up
on a platform to enhance its visual impact.
If the appliance is going to be installed
on carpeting, combustible linoleum tile or
other combustible material other than wood
fl ooring, the appliance must be installed on
a metal or wood panel extending the full
width and depth of the appliance.
4)
The G36D Direct Vent Gas Fireplace can be
installed in a recessed position or framed out
into the room as in A, B, C, D. See Diagram
1.
5)
This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6)
The G36D Direct Vent Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7)
We recommend that you plan your installation
on paper using exact measurements for
clearances and floor protection before
actually installing this appliance. Have a
qualifi ed inspector, dealer, or installer review
your plans before installation.
Note: For vent terminations see the
"Exterior Vent Termination Locations"
section.
A)
Flat on Wall
B)
Flat on Wall Corner
C)
Recessed into
Wall/Alcove
D)
Corner
G36D UNIT DIMENSIONS
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1)
Ensure that structural members are not cut
or weakened during installation.
2)
Ensure proper grounding using the #8
ground lug provided. Refer to the "Wiring
Diagram" section.