8.0 INSTALLATION
Publication No. 5111811
8.6 Condensate Drain (see section 7.6)
1. Connect the condensate drain using the 1” BSP
nut and seal supplied.
Ensure the discharge of condensate complies with
any national or local regulations in force (see
British Gas “Guidance Notes for the Installation of
Domestic Gas Condensing Boilers”.
2. The condensate outlet terminates in a 1” BSP nut
and seal for the connection of 21.5mm (
3
/
4
in) plastic
overflow pipe which should generally discharge
internally into the household drainage system. If this
is not possible, discharge into an outside drain is
acceptable.
8.7 Fitting The Flue
HORIZONTAL FLUE
1. The standard flue is suitable for lengths between
100mm minimum and 685mm maximum, as
measured from the edge of the flue elbow outlet to
the joint between the terminal and air duct (Fig. 23).
2. Locate the flue elbow on the adaptor at the top of
the boiler. Set the elbow to the required orientation
(Fig. 24).
NOTE: The flue elbow is angled at 93 degrees to
ensure a fall back to the boiler.
3. Measure the distance from the outside wall face to
the elbow. This dimension will be known as ‘X’
(Fig. 25).
4. To dimension ‘X’ add 50mm. This dimension to be
known as ‘Y’.
IMPORTANT: Check all dimensions before cutting.
Wall Thickness
(X)
Wall Thickness
(X)
Flue Elbow
Fig. 25
100mm
685mm
Fig. 23
Fig. 24
Adaptor