Baxi Potterton 24 Eco HE Boiler User Manual


 
7.0 SITE REQUIREMENTS
14
Publication No. 5111811
7.3 Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
2. BS 5440: Part 2 refers to room sealed appliances
installed in compartments. The appliance will run
sufficiently cool without ventilation.
7.4 Gas Supply
1. The gas installation should be in accordance with
the relevant standards. In GB this is BS 6891. In IE
this is the current edition of I.S. 813 “Domestic Gas
Installations”.
2. The connection to the appliance is a 22mm
copper tail located at the rear of the gas service
cock (Fig. 13).
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a
smaller diameter than the boiler gas connection
(22mm).
7.5 Electrical Supply
1. External wiring must be correctly earthed,
polarised and in accordance with relevant
regulations/rules. In GB this is the current I.E.E.
Wiring Regulations. In IE reference should be made
to the current edition of ETCI rules.
2. The mains supply is 230V ~ 50Hz fused at 3A
maximum.
NOTE: The method of connection to the
electricity supply must facilitate complete
electrical isolation of the appliance.
Connection may be via a fused double-pole
isolator with a contact separation of at least 3mm
in all poles and servicing the boiler and system
controls only.
Fig. 13
Gas Service Cock