Section 3 Entry Codes
SECTION 3: ENTRY CODES
The control panel is operated by Entry Codes, which are simple two digit numbers that provide
the panel instructions. However, before entering any codes, you should become familiar with
the features of the control panel.
The 8900SH has a keypad and a set of 6 display LED’s. A code is entered by simply pressing
any of the two digits on the keypad, which will then cause two LED’s on the far left to light up
in the order of the keys pressed. You must wait for the Entry Code in the display to begin
flashing before entering the desired temperature, value, code, etc.
The () star key on the lower left of the keypad cancels any code you have entered. If the
wrong code is entered, simply press the () key and start over.
IF THE PANEL DOES NOT POWER UP, OR THE RED DISPLAY LED’S ARE NOT ON,
REFER TO THE WIRING DIAGRAM AND INSTALLATION INSTRUCTIONS. ALSO, REFER
TO “SENSOR TROUBLESHOOTING” IN SECTION 5.
Below is a quick reference table showing the codes used to set up the control panel’s basic
operation. Do not be concerned that the codes are not listed in numerical order.
YOU MUST ENTER THE CODES IN THE ORDER SHOWN BELOW, THEN CALIBRATE ALL
SENSORS CONNECTED TO THE CONTROL PANEL. MORE DETAIL ON EACH CODE IS
AVAILABLE IN SECTION 8.
CODE FUNCTION
60
This code starts the sequence for the “60” codes.
62
This code displays the System Mode, which tells us that the boiler system is either ready to
heat or is shut off. Press 62 then press 0 (for System Off) or 1 (for System On).
63
This code manually overrides the control panel to control the boilers directly. Press Code 62
first, and enter 0, then press Code 63 and enter the number of the boiler you want to fire.
65
This code allows for the panel to control the system primary pump. After entering code 65,
entering 0 shuts the pump off, entering 1 starts the pump, and entering 2 automatically
cycles the pump. In the automatic cycle mode, the pump starts and stops along with the
boilers according to the system shutdown outdoor temperature chosen in code 21. Please
note that the pump starter must be an Automatic Reset type.
66
This code controls the temperature setback feature. When 66 is entered, the display will
show 0 or 1. Press 0 to turn it off, or press 1 to turn it automatically on.
67
This code displays the 24 hour (military) clock. Press 67, enter the hour and minutes, and
press # to save.
68
This code displays the day of the week and the day of the month. Press 68, enter the day of
the week and press #, then enter the day of the month, 01 to 31, and press #.