Smoke Detectors, 4-Wire:
1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Hochiki America SLG-12 with YBC-RL4-RA Base
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations and
thermostats may be used if acceptable to the Authority having Jurisdiction.
UL Compatible Smoke Detectors (Providing UL Recognition or Listing)
Manufacturer 4-Wire
Smoke Detector
2-Wire
Smoke Detector *
Smoke Detector
Base
Napco FW-4 FW-2
Sentrol
System
Sensor
449AT
449C
449CRT
449CST
449CSRT
449CSRH
449CSST
449CLT
449CSLT
449CTE
741U
742U
712U
722U
732U
711U
721U
721UT
731U
1112
2112
2112T
2112TSRB
2100
2100T
1100
701U
702U
702RE
702RU
Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10
SUMMARY OF UL REQUIREMENTS
Residential
Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.
FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)
Minimum alarm timeout of 5 minutes
Maximum exit time: 60 seconds
Maximum entry time: 45 seconds
Do not program “Swinger Shutdown”, “Auto-Bypass” or “50 ms Loop Response”
“Abort Delay” may not exceed 45 seconds
Program “Disable Callback Download”
Automatic dialer may not dial a police station number that has not been dedicated for such service
System must be tested at least weekly under AC/battery and Battery-Only conditions
Replace the rechargeable battery at least every 5 years
If the battery is heavily discharged, replace it or have it tested by a qualified technician
For silent panic, connect only to UL-listed holdup devices
All zones must be programmed for “Priority”
Do not program any zones for “Keyswitch Arming”
System must be serviced at least once every year
Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire”
Touchpad / Keypad Expansion (EZM) Zones are not to be used as fire zones
Touchpad / Keypad Auxiliary is not to be selected
The Freedom F-64 series Touchpads must have labels placed on only the appropriate Touchpad keys (Fire, Police and
Auxiliary) that are operational
Install in accordance with the NEC/CEC requirements
"Force Arm" and "Selective Bypass" must not be programmed for UL installations
UL Compatible Sounding Appliance:
Wheelock AH-12WP
Smoke Detectors & Summary of UL Requirements