Napco Security Technologies WI1501A Home Security System User Manual


 
Freedom F-64 Installation Instructions
L NAPCO Security Systems
WI1501A 9/06
Page 4
INTRODUCTION
GENERAL DESCRIPTION
Napco's Freedom F-64 is a state-of-the-art microcomputer-based burglary and residential fire alarm control panel of modular
design. Integrally an 8-zone panel, it will support up to 64 zones with the use of zone doubling, optional zone expansion
modules, wireless receiver modules and/or Freedom 64 Touchpads. Each panel includes an integral digital communicator.
The F-64 panel operates with the NAPCO Freedom 64 Touchpads, providing a complete Deadbolt-Activated Home Protection
System that combines intuitive interactive arming with passive disarming. The Touchpads provide a system which is not only
effortless to use, but also 100% false alarm resistant during the critical arming and disarming sequences. See WI1499 for
more information about the Freedom Touchpads.
The control panel features programmable area partitioning. That is, the system may be divided into up to 4 discrete multiple-
zone areas, each allowing access by only those users programmed for their respective area.
Opening Suppression and Closing Suppression, available through Napco Quickloader software, suppress reporting within
programmed “windows”. Conversely, Exception Reporting can transmit a “fail to close” if the panel is not armed within
programmed intervals and, similarly, a “fail to open” if the panel is not disarmed within programmed intervals. Furthermore, the
panel can be programmed to automatically arm either area at any time. A log containing up to 400 events (accessible through
Quickloader
TM
software) monitors control-panel activity referenced to a precision real-time clock. A detailed event history may
be displayed at the computer, using Napco’s PCD-Windows Quickloader Software.
Touchpads feature a liquid-crystal display for messages. In normal use, the LCD shows zone identification and status
messages, and the log can also be viewed. Conventional LEDs and a sounder are also provided for annunciation.
Data may be quickly and easily downloaded to the control panel using a PC-compatible computer with Napco's PCD-Windows
Quickloader software and PCI2000 computer interface. Or, the panel may be programmed using the F-64PROG program-
mer. In the programming modes (there are two: Dealer and User), the LCD shows memory address, data values,
programming prompts, and the alphanumeric characters required for entering up to 64 user codes and custom zone
descriptions. NOTE: Failure to install and program as described in this manual for UL Listed systems voids the
Listing Mark of Underwriters Laboratories, Inc.
FEATURES
Control Panel Features
Eight end-of-line-resistor burglary zones programmable
for Area (expandable to sixteen end-of-line resistors with
zone doubling or series zone doubling with loop supervi-
sion), Exit/Entry Delay, Interior (Stay) Bypass, Exit/Entry
Follower, Day Zone, Chime, Fire options, Swinger
Shutdown, Zone Anding and a variety of other features.
Supports up to 64 zones with optional zone-expansion
modules, wireless receiver modules and 4-zone Touch-
pads.
Supports up to 64 individually coded users.
Supports three outputs (Bell, PGM1 and PGM2) and up to
16 external outputs (using Relay Module RB3008,
RM3008 or the GEM-OUT8. See Relay Control in glos-
sary for more information).
Supports three Touchpad panics: Fire, Police & Auxiliary.
Supports four independent area partitions.
Supports up to seven separate access stations
(Touchpads) by up to 64 users.
Supports up to 16 separately-addressable X-10 devices
with the GEM-X10 KIT and PC04 interfaces.
English-language prompts & system status messages.
User Codes and Zone Descriptions outside assigned ar-
eas are able to be blocked from Touchpad display.
User-customized zone descriptions, re-programmable as
required.
Supports 2-wire and 4-wire smoke detectors.
Reports alarms, restores and troubles by zone.
400 Event Log.
Two programmable entry delay times.
One Interior Zone Group.
Dynamic battery test interrupts charging and places
battery under load every four hours.
Two Chimes by zone; programmable duration.
Quickloader programmable.
2 PGM outputs.
Supports Gemini Wireless Devices.
Communicator Features
Compatible with all major receiver formats, including 4/2,
SIA and Point ID (except Radionics Modem II).
Rotary dial and TouchTone
TM
with Rotary backup.
Three 20-digit telephone numbers.
Backup Reporting; Double Reporting; Split Reporting.
64 User Codes with Opening/Closing -Reporting by user.
AC Failure Reporting with programmable report delay.
Supervised telephone line with a fixed 60 second delay.
Pager capability.
F-64PROG Programmer Features
English-language LCD display; LED and sounder
annunciators.
Fault-Find diagnostics simplify troubleshooting.
SIA CP-01 Features.
See page 38 for complete information regarding how the
Factory Program complies with the Security Industry As-
sociation False Alarm Reduction Control Panel-01 Stan-
dard (SIA FAR CP-01).
Features