2. Selecting the unit
(1) Select the unit to be registered in the group selected in step 1.
• The address No. displayed in the operation No. display section will change in the following
order each time the TIME
switch is pressed. (The numbers will change in 10-unit
increments when the switch is held down.)
000 001
002 250
• The numbers will appear in reverse order when the TIME switch is pressed.
Address No. setting range Indoor unit, LOSSNAY : 001 to 050
Local remote controller : 101 to 200
Slave system controller : 000, 201 to 250
Operation No. display section: The address No. is displayed.
(2) When registered unit is selected
• The following will display when the selected unit is already registered in a group controlled
with this controller.
Example) When unit 011 (registered in group 23) is called with group 3
Pattern No. display section: The registered group No. and registered unit attributes alternately display.
3. Registering the unit into a group
(1) Register the unit selected in step 2 into a group.
• With the group No. and unit address selected in steps 1 and 2 displayed, press the
ON/OFF
switch.
• The registration process will be completed with this step.
• The address No. and attributes will appear when correctly registered.
Operation No. display section:
The address No. is displayed.
Pattern No. display section: The attributes are displayed when correctly registered.
Registration complete screen
The address 005 indoor unit is registered in group 3.
(2) Registering a separate unit
• Carry out steps 2 and 3 to register a different unit in the same group.
• Carry out steps 2 and 3 to register a unit in another group.
NOTE A LOSSNAY unit cannot be registered in a group containing indoor units. When registration is
attempted, these will not be correctly registered and "88" will flicker on the screen. If the indoor unit,
LOSSNAY, and local remote control are already registered in another group, they cannot be registered
in a different group. However, the slave system controller can also be registered in a different group.