Lochinvar 3.5 Boiler User Manual


 
3 Troubleshooting (continued)
51
Service Manual
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Outlet Temp
Shutdown
Outlet water temperature has exceeded the
maximum outlet water temperature.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the boiler is piped properly into the heating
system. Refer to Section 5 - Hydronic Piping of the
Crest Installation and Operation Manual
for the proper piping methods for the Crest boiler.
• Check for voltage to the boiler pump motor on a call
for heat. If voltage is not present, check wiring back
to the pump relay. Replace the pump relay if
necessary.
• If 120 VAC is present on a call for heat and the boiler
pump is not operating, replace the pump.
Watch Dog Error
The main control board has detected an
internal fault.
• Replace the main control board.
Write EEProm
The main control board has detected an
internal fault.
• Replace the main control board.
CRC Parameters
The main control board has detected an
internal fault.
• Replace the main control board.
No Error Stored
The main control board has detected an
internal fault.
• Press the RESET button on the SMART TOUCH
display panel.