Lochinvar 3.5 Boiler User Manual


 
1 Service (continued)
Service Manual
17
Parameter table
Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to
access them
Menu
Sub
Item
Parameter Name
(as shown on the LCD screen)
See
Page
Min
Max
Default
User Installer
Value Value Value Access Access
K
1 Boiler Pump Delay 24 0.5 2400 30 No Yes
2 Boiler Pump Anti-Seize Time 24 0 40 0.33 No Yes
3 Boiler Pump Mode 24 N/A N/A N/A No Yes
4 System Pump Mode 24 N/A N/A N/A No Yes
5 System Pump Delay 24 0.5 2400 30 No Yes
6 System Pump Anti-Seize Time 24 0 40 0.33 No Yes
7 HWG Pump Delay 24 0.5 2400 30 No Yes
8 HWG Pump Anti-Seize Time 24 0 40 0.33 No Yes
9 Delta T Setpoint 24 0 60 0 No Yes
L
1 Maintenance Notice - Months 25 0 36 12 No Yes
2 Maintenance Notice - Running Hours 25 0 100,000 10,000 No Yes
3 Maintenance Notice - Cycles 25 0 100,000 10,000 No Yes
4 Service Contact Number 25 N/A N/A N/A No Yes
5 Service Contact Name 25 N/A N/A N/A No Yes
PUMPS
SERVICE
NOTIFICATION