Lochinvar 3.5 Boiler User Manual


 
1 Service
Service Manual
14
Parameter table
Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to
access them
Menu
Sub
Item
Parameter Name
(as shown on the LCD screen)
See
Page
Min
Max
Default
User Installer
Value Value Value Access Access
C
7 Boost Time 20 0 250 20 No Yes
8 Boost Temperature 20 0 25 0 No Yes
9 Shift OA Reset Curve 20 -27 27 0 No Yes
D
1 Ramp Delay Mode 20 N/A N/A N/A No Yes
2 Ramp Delay Time #1 20 1 40 2 No Yes
3 Ramp Delay Time #2 20 1 40 2 No Yes
4 Ramp Delay Time #3 20 1 40 2 No Yes
5 Ramp Delay Time #4 20 1 40 1 No Yes
6 Ramp Delay Time #5 20 1 40 1 No Yes
7 Ramp Delay Time #6 20 1 40 1 No Yes
8 Ramp Delay Limit #1 20 10 100 20 No Yes
9 Ramp Delay Limit #2 20 10 100 30 No Yes
10 Ramp Delay Limit #3 20 10 100 40 No Yes
11 Ramp Delay Limit #4 20 10 100 55 No Yes
12 Ramp Delay Limit #5 20 10 100 75 No Yes
13 Ramp Delay Limit #6 20 10 100 100 No Yes
E
1 BMS Active/Inactive 21 ACTIVE INACTIVE INACTIVE No Yes
2 BMS Mode 21 POWER SETPOINT POWER No Yes
3 BMS Volts at Min Rate 21 0 10 2 No Yes
4 BMS Volts at Max Rate 21 0 10 10 No Yes
5 BMS Rate at Min Volts 21 4 100 4 No Yes
6 BMS Rate at Max Volts 21 0 100 100 No Yes
7 BMS Volts at Min Setpoint 21 0 10 2 No Yes
8 BMS Volts at Max Setpoint 21 0 10 10 No Yes
9 BMS Setpoint at Min Volts 21 32 185 68.9 No Yes
10 BMS Setpoint at Max Volts 21 32 185 178.7 No Yes
11 BMS Volts to Enable 21 0 10 2 No Yes
12 Differential to Stop BMS Demand 21 0 10 0.5 No Yes
13 BMS Enable Mode 21 ENABLE VOLTAGE VOLTAGE No Yes
OUTDOOR
RESET
RAMP DELAY
BMS