Lochinvar 3.5 Boiler User Manual


 
3 Troubleshooting (continued)
Service Manual
39
Table 3F Troubleshooting Chart - Noisy System
FAULT CAUSE CORRECTIVE ACTION
Noisy
Operation
- Supply gas problem. Natural and LP gas
pressures should be between 4 inches w.c.
(1.0 kPa) and 14 inches w.c. (3.5 kPa).
Refer to Section 6 - Gas Connections of the Crest
Installation and Operation Manual for detailed
information concerning the gas supply.
- Gas/air mixture problem. Refer to the Gas Valve Adjustment Procedure on
page 53 of this manual for the proper gas valve setting.
Verify that the vent/air intake lengths do not exceed the
maximum listed in the General Venting section of the
Crest Installation and Operation Manual.
- Dirty/damaged burner. • Refer to page 34 in this manual for the burner removal
and inspection procedure. Clean or replace the burner
as necessary.
- Air in the piping system. • Properly purge all air from the piping system.
No Pump
Operation -
Boiler Pump
System Pump
or
HWG Pump
- Blown fuse.
• Replace fuse F4 on the control board, see page 36 of
this manual.
- Faulty pump.
• Replace pump.
- Internal fault on control board.
• Replace main control board.
- Faulty pump relay.
• Replace relay.
- Incorrect parameter setting.
Reference the Boiler Pump Mode and System
Pump Mode parameters in the Service section of this
manual.
Relief Valve
Opening
- System pressure exceeds relief valve
setting.
Lower the system pressure below the rating of
the supplied relief valve or replace the standard relief
valve with a higher rated valve up to the maximum
pressure of the heat exchanger 160 psi (40 kPa).
• Improperly sized expansion tank.