Lochinvar 000 - 260 Boiler User Manual


 
43
Installation & Service Manual
Maintenance and annual startup
Service technician
(see the following pages for instructions)
General:
Address reported problems
Inspect interior; clean and vacuum if
necessary;
Check for leaks (water, gas, flue)
Examine venting system
Check system water pressure/system
piping/expansion tank
Check control settings
Check wiring and connections
Flame inspection (stable, uniform)
Check flue gas passageways
Inspect and clean the burners
Perform start-up checkout and
performance verification per Section 6 -
Start-up.
If combustion or performance
indicate need:
Clean heat exchanger
Remove and wash burners
ANNUAL START-UP
Owner maintenance
(see the User’s Information Manual for instructions)
Daily
• Check appliance area
Check pressure/temperature
gauge
Monthly
• Check vent piping
• Check relief valve
Periodically
• Test low water cutoff (if used)
• Reset button (low water cutoff)
Every
6 months
• Check appliance piping (gas and
water) for leaks
• Operate relief valve
End
of season
months
•Shut appliance down (unless
boiler used for domestic hot
water)
Table 7A_Service and Maintenance Schedules
7 Maintenance