Lochinvar 000 - 260 Boiler User Manual


 
Installation & Service Manual
38
Outdoor Air Reset Option
For boilers ordered with the Outdoor Air Reset option, there
is an additional control (FIG. 5-5). There are three setting
knobs for Shutdown, Outdoor Air Max., and Ratio. There is
also a switch to turn the outdoor air shutdown feature On or
Off. An O.A. Sensor is also included.
R4R4
R6R6
R8R8
R16R16
R15R15
C7C7
C9C9 C10C10
VR2VR2
VR3VR3
OJ1OJ1
OJ2OJ2
D4D4
J4J4
CN1CN1
CN2CN2
CN9CN9
CN7CN7
CN8CN8
CN3CN3
CN4CN4
CN5CN5
CN6CN6
W1W1
TST2314TST2314
2020
1515
1010
55
(F-)0(F-)0
1515
1414
1313
1212
1111
10
99
88
77
66
55
OFFOFF
120120
240240
220220
200200
160160
140140
SETPOINTSETPOINT
DIFFERENTIALDIFFERENTIAL
HIGH-FIREHIGH-FIRE
OFFSETOFFSET
(c)2002 L.C.(c)2002 L.C.
SHUTDOWN
45
50
45
1.3
O.A. MAX.
70
40
VR1
65
RATIO
VR2
0.6
0.5
0.7
1.4
1.5
W1 W2
W3
60
50
7040
55
60
VR3
65
DISABLE
O.A. SHUTDOWN
1.0
0.9
0.8
1.2
1.1
O.A. SENSOR
ENABLE
ON
SW1
55
CN1
Shutdown
The Shutdown knob specifies the outdoor air lockout
temperature at which the control would prevent the unit from
operating.
Outdoor Air Max (O.A. Max)
The O.A. Max knob allows a reset up to the maximum
outdoor air temperature specified by this knob setting. When
the outdoor air temperature is above the specified setting, the
unit will not function in the O.A. Reset Mode, but will
continue to run at the selected set point temperature.
Note that the set point knob will now indicate the “minimum”
boiler temperature. Target temperature is determined by the
ratio and outdoor air temperature below the O.A. Max
setting.
Ratio
The Ratio knob allows control over the reset ratio to be used
during Outdoor Air Reset. The allowable ratios are as low as
0.5:1 or as high as 1.5:1.
Selecting the 0.5:1 ratio will increase the set point 0.5° for
every 1.0° drop in outdoor air temperature up to the
maximum set point temperature.
Selecting the 1.5:1 ratio will increase the set point 1.5° for
every 1.0° drop in outdoor air temperature up to the
maximum set point temperature.
If the outdoor design and boiler design temperatures are known,
the Ratio setting can be calculated using the following formula:
Ratio = (boiler design temperature - operator set point)
(O.A. Max. setting - outdoor design temperature)
Note that the reset set point cannot exceed the maximum set
point of the boiler thermostat.
These settings are illustrated graphically in FIG. 5-6.
Figure 5-5_Optional Outdoor Air Reset Control
Figure 5-6_Outdoor Air Control Example Chart
Outdoor Air Shutdown Enable/Disable Switch
The Outdoor Air Shutdown Enable/Disable switch turns the
outdoor air shutdown feature On and Off. Disabling the
Outdoor Air Shutdown feature allows the unit to operate
regardless of the outdoor air temperature. This is needed for
indirect domestic hot water systems for example.
Additional Temperature Controls
High Water Temperature Limit Con trol
The appliance is supplied with a fixed setting, auto-reset high
water temperature limit control. The setting of this control
limits max i mum discharge water tem per a ture. If water
temperature exceeds the setting, the limit will break the con trol
circuit and shut down the appliance. The limit control will only
be reset after the water tem per a ture has cooled well below the
setting of the limit. The auto-reset high water temperature limit
control is mount ed in the outlet side of the front header.
5 Electrical connections