IDEAL INDUSTRIES HE18 Boiler User Manual


 
24
icos - Installation & Servicing
INSTALLATION
FLUE OUTLET
rf8394-1
690mm
Fixed
300mm
min
30
FLUE TERMINAL POSITION
rf8393-1
300mm
min
300mm
min
625mm
Fixed
Flat roof - with structure
The terminal should be positioned so that products of
combustion can safely disperse at all times.
Pluming may occur at the termination so, where
possible, terminal positions where this could cause
a nuisance should be avoided.
Minimum dimensions are shown below
Terminal Position Minimum Dimension
Directly below an opening,
air brick, windows, etc. 300 mm
Below plastic / painted gutters 300 mm
Painted surface 300 mm
Below eaves or balcony 500 mm
rf8392