47Heat & Glo • XLR-N-CE, XLR-PB-CE • 2198-900 Rev. J • 5/12
B. MantelandWallProjections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specied. Framing closer than the
minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc.)
Failure to comply could cause re.
Figure13.5 ClearancesToCombustibleMantelsOrOther
CombustiblesAboveAppliance
Mantels(Combustible/Non-Combustible)
Figure13.6Non-CombustibleMantelLegorWallProjections
(Acceptableonbothsidesofopening)
UNLIMITED
TOP VIEW
18 cm
8 cm
MINIMUM
36 cm
MIN.
30 cm
MAX.
1,3 cm
Thick Wall
Sheathing
MEASUREMENT
FROM TOP OF
FIREPLACE
OPENING
Note:For non-combustible replace nish material (marble,
stone, etc) specications refer to Section 13.C.
MantelLeg(Combustible/Non-Combustible)
C. FacingMaterial
• Facing and/or nishing materials must not interfere with
air ow through louvers, operation of louvers or doors,
or access for service.
• Facing and/or nishing materials must never overhang
into the glass opening.
• Observe all clearances when applying combustible
materials.
Figure13.7OverlapFitMethod(TonicorMartiniDecorative
Front)
FACTORY-INSTALLED
NON-COMBUSTIBLE BOARD
DRYWALL OR
EQUIVALENT (1,2 cm)
NON-COMBUSTIBLE
FINISHING MATERIAL
0 - 2,5 cm THICK
NON-COMBUSTIBLE
FINISHING MATERIAL
0 - 2,5 cm THICK
TONIC DECORATIVE
FRONT SHOWN
3,8 cm ABOVE STANDOFF
Both the Tonic and Martini decorative fronts can be in-
stalled with an “Overlap” or “Inside Fit” method:
Overlap Requirement: See Figure 13.7.
Inside Fit requirement: See Figure 13.8 and 13.9.
Non-CombustibleFinishMaterials
0-2,54cmThickness-OverlapFitMethod
Both the Tonic and Martini decorative fronts are designed
to overlap nish materials 0 cm to 2,54 cm thick. See
Figure 13.6.
NOTICE: This 2.54 cm maximum not only includes the
decorative nish materials (marble, tile, slate, etc) but
also the mortar or adhesive used to attach the decorative
nish material.
The non-combustible nish material can be installed up to
the replace opening.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specied in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.
WARNING! Risk of Fire! DO NOT install drywall or other
combustible materials over the factory-installed non-com-
bustible board. Overlapping materials could ignite.
Decorative facing material thickness is measured from
the face of the factory-installed non-combustible board.
See Figure 13.7