21Heat & Glo • XLR-N-CE, XLR-PB-CE • 2198-900 Rev. J • 5/12
A. VentTerminationMinimumClearances
Figure6.1MinimumHeightFromRoofToLowestDischarge
Opening
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
VERTICAL
WALL
TERMINATION
CAP
HORIZONTAL
OVERHANG
30,5 cm
X
ROOF PITCH
IS X/ 30,5 cm
LOWEST
DISCHARGE
OPENING
51 cm
6
TerminationLocations
Fire Risk.
Maintain vent clearance to combustibles as
specied.
• DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause overheating and re.
WARNING
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Termination
Cap **
A*
*
If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
**
In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be
higher than the gas termination cap.
A B
15,2 cm (minimum) up to 50,8 cm
45,7 cm minimum
50,8 cm and over 0 cm minimum
Figure6.2 StaggeredTerminationCaps
Angle H(Min.)cm
0°-26.6° .......................................................... 30*
26.6°-30.3° .......................................................... 38*
30.3°-33.7° .......................................................... 46*
33.7°-36.9° .......................................................... 61*
36.9°-39.8° .......................................................... 76
39.8°-42.5° .......................................................... 99
42.5°-45.0° ........................................................1 22
45.0°-49.4° ........................................................1 52
49.4°-53.1° ........................................................1 83
53.1°-56.3° ........................................................2 13
56.3°-59.0° ........................................................2 29
59.0°-60.3° ........................................................2 44
*.91 M minimum in snow regions