Heat & Glo LifeStyle Exclaim-50 Indoor Fireplace User Manual


 
42

Refer to Sections 11.A. and Sections 11.B. for combus-
tible/non-combustible materials. Refer to Figure 11.9 for
non-combustible zone.
WARNING! Risk of Fire! You must maintain clearances.
Use only non-combustible framing material below
standoffs.
Sheetrock, wood or other combustibles must NOT be
used as sheathing or facing in the non-combustible
zone.
DO NOT cover metal replace front with combustible
materials.
Install combustible materials only to specied clearances
on top front and side edges.
Complete framing and apply facing material (drywall)
over framing.
A bead of 300-deg F minimum non-combustible sealant
must be used to close off any gaps at the top and sides
between the replace and facing to prevent cold air
leaks.
Large gaps can be bridged with fiberglass rope
gasket.
Only non-combustible materials may be used to cover
the metal replace front.
These surfaces
may be covered
with non-combustible
material.
Non-combustible
sealant.
 
Metal strips are placed 2 in. (51 mm)
under the front of the fireplace and must
extend beyond the front and sides of
fireplace opening by 2 in. (51 mm)
Continuous,
non-combustible sealant
Floor constructed of wood or
other combustible material
1/2 in. Micore
or equivilent
insulation
Finished combustible wall
Combustible material
Non-combustible
decorative facing
(up to full brick depth)
2 x 4 header, flush with
front of stand-offs
Tile, stone or other
non-combustible material
Flat 2 x 4 stud wall

Heat & Glo • EXCLAIM-50 • 4013-041 • Rev AA • 7/12