Heat & Glo LifeStyle ESCAPE-I35-C Heating System User Manual


 
23
Heat & Glo • Escape-I35-C, Escape-I30-C • 2201-901 Rev. H • 5/12
B. Venting Components
CAUTION! Risk of Cuts/Abrasions/Flying Debris.
Wear protective gloves and safety glasses during instal-
lation. Sheet metal edges are sharp.
The vertical vent termination system installed on this model
includes:
One 3-foot section stainless steel exible pipe (included
with insert).
Flexible vent pipe for exhaust air (included with vent kit).
• One length of 3-inch exible vent pipe for combustion
air (included with vent kit).
• One pipe-to-cap adaptor (included with vent kit).
• One vertical termination cap (included with vent kit).
8
8
Installing Vent Pipe and Appliance
Figure 8.1
WARNING! Risk of Fire/Explosion/Asphyxiation! Do
NOT connect this gas appliance to a chimney ue serving
a separate solid fuel or gas burning appliance.
• May impair safe operation of this appliance or other
appliances connected to the ue.
• Vent this appliance directly outside.
Use separate vent system for this appliance.
Horizontal venting is NOT allowed.
Vertical terminations are measured to top of chimney.
This appliance is listed for use with LINK-DV systems
and components only. It is permissible to extend venting
above existing chimney (within speci ed maximum verti-
cal limits) using SL-D series or Dura Vent GS series 4 in.
x 6-5/8 in. gas direct-vent pipe. Connection is made us-
ing DV-46DVA-GK. The vent must be terminated with the
cap supplied with the LINK-series vent kit.
A. Vent Limits
The abbreviations listed in this vent table key are used in
the vent diagrams.
Description
Minimum Vertical Run Length 10 ft.
Maximum Vertical Run Length 50 ft.
CAUTION! ALL vent speci cations MUST be followed.
This product is tested and listed to these speci cations.
Appliance performance will suffer if speci cations are not
followed.
EXHAUST
AIR
VENT PIPE
TERMINATION
CAP
EXHAUST STARTING COLLAR
STARTING COLLAR BRACKET
INLET AIR STARTING COLLAR
INLET AIR
VENT PIPE
ADAPTER
V = 10 FT. MINIMUM
50 FT. MAXIMUM
NOTE: TO ACHIEVE OPTIMUM PERFORMANCE,
MINIMIZE OR AVOID BENDS IN EXHAUST VENT
PIPE.
EXHAUST
COLLAR
INLET
COLLAR
HANDLE
EXHAUST
STARTING
COLLAR
INLET AIR
STARTING
COLLAR
STARTING
COLLAR
BRACKET
LOCKING TAB