Installation Preparation
Prepare the existing solid fuel masonry or factory built
non-combustible rebox for installation.
A. Inspection and Cleaning
Prior to installing the gas insert:
• Have the chimney and adjacent structure inspected
and cleaned by quali ed professionals. Hearth & Home
Technologies recommends that NFI or CSIA certi ed
professionals, or technicians under the direction of certi-
ed professionals, conduct a minimum of a NFPA 211
Level 2 inspection of the chimney.
Replace component parts of the chimney and replace
as speci ed by the professionals.
Ensure all joints are properly engaged and the chimney
is properly secured.
• Ensure combustible mantel and surround clearances
comply with applicable codes and regulations for solid-
fuel replaces. In the absence of local or regional codes,
refer to NFPA 211.
• Ensure chimney is constructed of non-combustible
materials.
• Ensure chimney is clean and in good working order.
Ensure that all chimney cleanouts t properly to prevent
air leakage into chimney.
B. Flue Damper
Fully lock the solid fuel replace’s ue damper in the open
position, OR completely remove it.
C. Gas Line
Note: If the factory built replace has no gas access hole
provided, an access hole of 1 inch (25 mm) diameter or
less may be drilled through the lower sides or bottom of the
rebox in a proper workmanship - like manner. This access
hole must be plugged with non-combustible insulation after
the gas supply line has been installed.
• Install gas line into rebox cavity.
• Check local codes and gas line sizing requirements
following NFPA51. See Section 9.
E. Electrical Outlet Box
An outlet box may be installed in a bottom back corner of
the existing solid fuel masonry or factory built replace to
permit blowers or other optional accessories to be used.
Alternatively, the supplied power cord may be routed out
onto the hearth to a nearby outlet.
D. Fireplace Conversion Notice
Permanently attach the label with the following warning to
the inside lower back of the replace rebox into which the
insert is being installed. Silicone or mechanical fasteners
may be required to properly secure the label.
WARNING! Risk of Fire! This replace has been con-
verted for use with a gas replace insert only and cannot
be used for burning wood or solid fuels unless all original
parts have been replaced, and the replace re-approved
by the authority having jurisdiction.
F. Remote Control Con guration
The Intelli re Plus
TM
should be programmed to the RC300
remote control prior to the installation of the insert into the
existing solid fuel masonry or factory built replace.
The control is accessed by removing the lower access
panel on the left side of the insert. See Section 10.E for
details.