Fireplace Size Requirements
A. Minimum Fireplace Opening
Minimum replace opening requirements are shown in
Figure 5.2.
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access.
Due to high temperatures, the appliance should be locat-
ed out of traf c and away from furniture and draperies.
• The rebrick (refractory), glass doors, screen rails, screen
mesh and log grates can be removed from a factory
built rebox in order to gain minimum gas insert opening
requirements.
Any smoke shelves, shields and baf es may be removed
from the factory built rebox if attached with mechanical
fasteners.
• The metal oor of the solid fuel rebox may be removed
to facilitate the installation of the insert.
Cutting of any sheet metal parts of the replace in which
the gas replace insert is to be installed is prohibited,
except the oor as tested for and as noted above and in
Figure 5.1.
• A minimum 1/2 inch gap from the bottom of the
appliance to the metal oor of the solid fuel rebox is
RECOMMENDED for optimal fan performance. See
side view in Figure 5.1.
1/2 IN. MINIMUM LEVELING HEIGHT
(RECOMMENDED)
1/4 IN. REQUIRED
12 IN.
5 IN.
6 IN.
11-1/4
IN.
TOP VIEW
SIDE VIEW
EXISTING FACTORY BUILT FIREBOX
ESCAPE-I35-C
ESCAPE-I30-C
METAL FLOOR OF EXISTING SOLID FUEL FIREBOX
REMOVE THIS
SECTION OF
METAL FLOOR
METAL FLOOR OF EXISTING
SOLID FUEL FIREBOX
REMOVE THIS
SECTION OF
METAL FLOOR
5 IN.
11-1/4
IN.
6 IN.
12 IN.
Figure 5.1-A
The appliance may not be placed directly on the base of
the outer wrap, a 1/4 inch airspace MUST be provided
between the insert and the oor of the outer wrap. Use
the levelling legs to raise the insert a minimum of 1/4 inch.
The original replace may never be returned to solid
fuel in this condition. The sidewalls and top structure
of the rebox may not be altered with the exception of
removable baf es and dampers.
If the recommended 1/2 inch leveling leg height can not
be achieved, a section of the factory-built metal oor may
be removed. See Figure 5.1-B.
Figure 5.1-B