Home Automation 20A00-1 Home Security System User Manual


 
Page 45
CALL BACK PHONE NUMBER
In response to a request for remote PC ACCESS using the PC ACCESS code, the system will hang up and dial this number back
immediately. To program the CALLBACK PHONE NUMBER, enter the number then press ' # '. To remove the CALLBACK
PHONE NUMBER, press the OFF key to enter a single "-", then press ' # '.
CALL BACK PHONE NUMBER:
-
OUTSIDE SIREN DELAY
If an output is configured as an "Exterior Sounder", when the alarm is "tripped", the interior sounder is turned on first. After the
OUTSIDE SIREN DELAY, the outside sounder is turned on.
This feature helps reduce annoying false alarms by signaling inside the premises first. The outside siren delay is set to 15 seconds
at the factory. You may change it to any value from 0 to 60 seconds. If you want the outside sounder to turn on immediately
when the alarm is activated, set the delay to 0. We recommend a minimum time of 15 seconds.
DIAL OUT DELAY: 15
0-60 SECONDS
DIAL OUT DELAY
The DIAL OUT DELAY is the number of seconds that the Omni II waits before making an emergency dial out, AFTER the alarm
is "tripped" (activated by burglar or fire). This delay is set at the factory to 15 seconds. We recommend a minimum time of 15
seconds to preclude an accidental activation of the alarm from calling in a false alarm.
DIAL OUT DELAY: 15
0-60 SECONDS
ALARM RESET TIME
The Alarm Reset Time is the time it takes before the alarm system resets itself after the alarm is tripped.
ALARM RESET TIME: 4
1-30 MINUTES
To change the alarm reset time, enter a new time between 1-30 minutes, then press the ' # ' key. The default setting is 4 minutes.
ARMING CONFIRMATION
The Arming Confirmation is a quick pulse (squawk) given by the outside siren when the alarm system is armed into a security
mode and the EXIT DELAY is expired.
ARMING CONFIRMATION: 0
0=NO 1=YES
To enable the arming confirmation feature, press the 1 (YES) key, then press the ' # ' key. The default setting is 0 (NO) disabled.
FIRE ALARM VERIFICATION
This unit is equipped with a FIRE ALARM VERIFICATION feature. When a zone configured as a FIRE (Type 32) or a GAS
(Type 34) is activated, the system will cycle SWITCH 12V and Switched Power Outputs off for 10 seconds. The SWITCH 12V
power output will then be restored, and 5 seconds later, the zones will be monitored again. If the zone is activated again within a
2-minute window, the fire alarm will be activated. If not, no fire alarm will be indicated.
VERIFY FIRE ALARMS: 1
0=NO 1=YES