Home Automation 20A00-1 Home Security System User Manual


 
Page 37
FIRE TAMPER
This zone type is used to monitor the wiring to bells and sirens (other than those connected to the Horn Output). The zone will
report trouble if an open, short, or other wiring problem is detected in the supervised bell circuit. This zone will make a digital
dial out when violated. Connect a wire from the Fire Tamper zone (+) to an output configured as a Sounder.
AUXILIARY
A zone defined as AUXILIARY is ignored for security. It is used to activate macros or to conditionalize programs. This is the
default setting for all zones. Zones that are not in use should be configured as AUXILIARY.
KEYSWITCH INPUT
This zone is used to arm AWAY and Disarm the Omni II security system using a toggle (to ground) keyswitch or keypad.
PROGRAMMABLE ENERGY SAVER MODULE
This zone type is for use with the Programmable Energy Saver Modules (PESM). It converts the Zone and the corresponding
Output to operate the PESM. Only Zones 9-16 can be programmed as a PESM.
OUTDOOR TEMPERATURE
Use this zone type for Outdoor Temperature Sensors. The outdoor temperature can be displayed on the console, spoken over the
telephone, or displayed on an HAI Communicating Thermostat.
TEMPERATURE
The general-purpose TEMPERATURE ZONE type is typically used to monitor indoor temperatures and control devices. It sets
the zone secure/not ready for program conditionals and event button activation.
If FREEZE ALARM is enabled, it reports a potential freeze condition if the temperature falls below 40
o
.
TEMPERATURE ALARM
The TEMPERATURE ALARM ZONE type will generate an alarm (console beeper, no sirens) and dial out if the temperature
goes above the high setpoint or drops below the low setpoint.
HUMIDITY
The HUMIDITY ZONE type is used to monitor indoor and outdoor humidity levels from 0 to 100 percent using the Model
31A00-2 Indoor/Outdoor Temperature and Humidity Sensor. It sets the zone secure/not ready state for program conditionals and
event button activation programs.
NOTE ON TEMPERATURE AND HUMIDITY ZONE TYPES
Outdoor temperature, temperature, and temperature alarm zone types all have HEAT (LOW) and COOL (HIGH) setpoints. The
zone is "Not Ready" when the temperature is above the high setpoint or below the low setpoint. The zone is "Secure" when the
temperature is between the setpoints. Setting a setpoint to 0 disables the setpoint.
Except for a type 83, the alarm is not activated. The zone "Not Ready" or "Secure" status is used to activate button programs and
program conditionals.