Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump Heat Pump User Manual


 
24
HEATING PERFORMANCE DATA
GSH130[48-60]4AC
High pressure is measured at the suction service valve ( the larger valve). AMPS = Outdoor unit amps (comp.+fan)
Low pressure is measured at the gauge port connection. KW = Total system power
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches exter-
nal static pressure on coil of outdoor section. Indoor air cubic feet per
minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will
occur in indoor air temperature drop (Delta T). Low and high side
pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor
temperature drop (Delta T). A slight decrease will occur in low and
high side pressures and power.
A properly operating unit should be within plus or minus 2 degrees of
the subcooling value shown in the Heat Pump Specifications.
A properly operating unit should be within plus or minus 3 degrees of
the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI
PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO
PR shown.
A properly operating unit should be within plus or minus 3 Amps of the
typical value shown.
EXPANDED PERFORMANCE DATA
MODEL: GSH13048-3A* / ARUF61-00*-1* / ARUF48601A* HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 54.1 51.2 48.2 45.0 43.0 41.7 38.7 35.7 33.6 31.1 28.6 27.0 26.0 23.3 20.7 18.0 15.4 12.6
Delta T30.629.027.325.524.423.621.920.219.117.616.215.314.713.211.710.2 8.7 7.1
KW 4.11 4.04 3.96 3.88 3.84 3.81 3.73 3.65 4.07 3.98 3.89 3.84 3.80 3.71 3.62 3.53 3.44 3.35
AMPS 8.6 8.1 7.7 7.3 7.1 7.0 6.7 6.4 6.2 6.0 5.8 5.7 5.6 5.4 5.2 5.0 4.7 4.4
COP 3.853.713.563.393.283.203.032.862.422.282.152.062.001.841.671.491.311.10
EER 13.1 12.7 12.2 11.6 11.2 10.9 10.4 9.8 8.3 7.8 7.3 7.0 6.8 6.3 5.7 5.1 4.5 3.8
HI PR 252 242 232 222 217 213 205 196 188 180 173 168 165 159 153 147 141 136
LO PR 76 71 66 61 57 55 51 45 41 36 32 30 29 24 21 18 15 12
MODEL: GSH13060-3A* / ARUF61-00*-1* / ARUF48601A* HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 69.8 66.0 62.2 58.1
55.5
53.8 50.0 46.1 43.6 40.3 37.1 35.0 33.7 30.2 26.8 23.4 20.0 16.3
Delta T34.332.530.628.627.326.424.622.721.419.818.217.216.614.913.211.5 9.8 8.0
KW 5.25 5.15 5.05 4.95
4.89
4.85 4.75 4.65 5.20 5.08 4.96 4.89 4.84 4.72 4.61 4.49 4.37 4.25
AMPS 10.5 9.8 9.3 8.9 8.6 8.5 8.1 7.7 7.5 7.2 7.0 6.8 6.8 6.5 6.2 5.9 5.6 5.2
COP 3.893.753.603.443.323.253.082.902.462.322.192.092.041.871.701.521.341.12
EER 13.3 12.8 12.3 11.7 11.3 11.1 10.5 9.9 8.4 7.9 7.5 7.2 7.0 6.4 5.8 5.2 4.6 3.8
HI PR 270 258 248 238 232 228 219 210 201 192 184 180 177 170 164 157 151 146
LO PR 77 71 67 61 58 56 51 46 41 37 32 30 29 25 21 18 16 12
MODEL: GSH130483B*, 484A* / AR*F496016B HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 60.1 56.9 53.6 50.1
47.8
46.3 43.0 39.7 35.9 33.1 30.5 28.8 27.7 24.9 22.1 19.2 16.4 13.5
Delta T 34.8 32.9 31.0 29.0 27.7 26.8 24.9 23.0 20.8 19.2 17.7 16.7 16.1 14.4 12.8 11.1 9.5 7.8
KW 4.54 4.43 4.33 4.23
4.17
4.12 4.02 3.92 3.55 3.45 3.35 3.30 3.26 3.16 3.07 2.97 2.87 2.78
AMPS 13.6 12.6 11.8 11.2 10.8 10.6 10.0 9.6 9.2 8.8 8.4 8.2 8.1 7.7 7.3 6.9 6.4 5.8
COP 3.883.763.623.473.363.293.132.972.962.812.662.562.492.302.111.891.671.42
EER 13.2 12.8 12.4 11.9 11.5 11.2 10.7 10.1 10.1 9.6 9.1 8.7 8.5 7.9 7.2 6.5 5.7 4.8
HI PR 266 255 245 234 229 224 216 207 198 189 182 178 174 168 161 155 149 144
LO PR 77 71 67 61 58 56 51 46 41 37 32 30 29 24 21 18 16 12