High pressure is measured at the suction service valve ( the larger valve). AMPS = Outdoor unit amps (comp.+fan)
Low pressure is measured at the gauge port connection. KW = Total system power
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
HEATING PERFORMANCE DATA
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature
MODEL: GSH13048-3A* / ARUF61-00*-1* / ARUF48601A* HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 54.1 51.2 48.2 45.0
43.0
41.7 38.7 35.7 33.6 31.1 28.6 27.0 26.0 23.3 20.7 18.0 15.4 12.6
Delta T31.329.627.926.124.924.122.420.719.518.016.515.615.013.512.010.4 8.9 7.3
KW 3.71 3.64 3.57 3.50
3.45
3.42 3.35 3.28 3.34 3.26 3.19 3.14 3.11 3.04 2.96 2.89 2.81 2.74
AMPS 14.6 13.6 12.7 12.0 11.6 11.3 10.7 10.2 9.8 9.3 8.9 8.7 8.6 8.2 7.7 7.2 6.7 6.1
COP 4.26 4.11 3.95 3.77 3.64 3.56 3.38 3.18 2.95 2.79 2.63 2.51 2.44 2.25 2.04 1.83 1.60 1.35
EER 14.6 14.1 13.5 12.9 12.4 12.2 11.5 10.9 10.1 9.5 9.0 8.6 8.4 7.7 7.0 6.2 5.5 4.6
HI PR 224 215 206 197 193 189 182 174 167 159 153 149 147 141 136 130 126 121
LO PR 73 68 64 58 55 53 49 44 39 35 31 29 28 23 20 17 15 12
MODEL: GSH13060-3A* / ARUF61-00*-1* / ARUF48601A* HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 69.8 66.0 62.2 58.1 55.5 53.8 50.0 46.1 43.6 40.3 37.1 35.0 33.7 30.2 26.8 23.4 20.0 16.3
Delta T 35.9 34.0 32.0 29.9 28.5 27.7 25.7 23.7 22.4 20.7 19.1 18.0 17.3 15.6 13.8 12.0 10.3 8.4
KW 5.58 5.47 5.35 5.24 5.17 5.12 5.01 4.89 4.37 4.27 4.17 4.11 4.07 3.96 3.86 3.76 3.65 3.55
AMPS 22.1 20.4 19.1 18.0 17.3 17.0 16.0 15.2 14.5 13.9 13.2 12.9 12.7 12.1 11.2 10.6 9.8 8.8
COP 3.66 3.54 3.40 3.25 3.14 3.07 2.92 2.75 2.92 2.76 2.60 2.49 2.43 2.23 2.03 1.82 1.60 1.35
EER 12.5 12.1 11.6 11.1 10.7 10.5 10.0 9.4 10.0 9.4 8.9 8.5 8.3 7.6 6.9 6.2 5.5 4.6
HI PR 273 262 252 241 235 231 222 213 204 195 187 182 179 172 166 159 153 148
LO PR 72 67 63 58 54 52 48 43 39 35 30 28 27 23 20 17 15 11
GSH130[36-48]3AE; GSH130363AF
GSH130603AC
EXPANDED PERFORMANCE DATA
MODEL: GSH13036-3AE / ARUF49-00*-1* / ARUF36421A* HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 40.2 38.1 35.8 33.5 32.0 31.0 28.8 26.6 19.9 18.4 16.9 16.0 15.4 13.8 12.3 10.7 9.1 7.5
Delta T 29.2 27.7 26.0 24.3 23.2 22.5 20.9 19.3 14.5 13.4 12.3 11.6 11.2 10.0 8.9 7.8 6.6 5.4
KW 2.80 2.75 2.70 2.64 2.61 2.59 2.54 2.49 2.47 2.41 2.36 2.33 2.31 2.25 2.20 2.15 2.09 2.04
AMPS 11.0 10.2 9.6 9.1 8.7 8.6 8.1 7.7 7.4 7.1 6.8 6.6 6.5 6.2 5.8 5.5 5.1 4.7
COP 4.204.053.893.713.583.503.323.132.362.232.102.011.951.791.631.461.271.07
EER 14.4 13.9 13.3 12.7 12.2 12.0 11.3 10.7 8.1 7.6 7.2 6.9 6.7 6.1 5.6 5.0 4.4 3.7
HI PR 219 210 202 193 189 185 178 171 164 156 150 146 144 138 133 128 123 119
LO PR 78 72 67 62 58 56 52 46 42 37 33 30 29 25 21 18 16 12
MODEL: GSH13036-3AF/ ARUF49-00*-1* / ARUF36421A* HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 37.2 35.3 33.2 31.0
29.6
28.7 26.7 24.6 23.5 21.7 20.0 18.8 18.1 16.3 14.4 12.6 10.7 8.8
Delta T 28.3 26.8 25.2 23.6 22.5 21.8 20.3 18.7 17.9 16.5 15.2 14.3 13.8 12.4 11.0 9.6 8.2 6.7
KW 2.64 2.58 2.53 2.47
2.44
2.42 2.36 2.31 2.44 2.38 2.32 2.28 2.26 2.19 2.14 2.08 2.01 1.96
AMPS 7.5 7.0 6.6 6.2 6.0 5.9 5.6 5.3 5.1 4.9 4.7 4.6 4.6 4.4 4.1 3.9 3.6 3.3
COP 4.133.993.843.673.553.483.303.122.822.672.522.422.352.171.981.771.561.32
EER 14.1 13.6 13.1 12.5 12.1 11.9 11.3 10.7 9.6 9.1 8.6 8.3 8.0 7.4 6.8 6.1 5.3 4.5
HI PR 213 204 196 188 183 180 173 166 159 152 146 142 140 134 129 124 120 115
LO PR 61 57 53 49 46 44 41 36 33 29 26 24 23 19 17 14 12 10