Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump Heat Pump User Manual


 
11
COOLING PERFORMANCE DATA
GSH130483AE
EXPANDED PERFORMANCE DATA
COOLING OPERATION
MODEL: GSH130483A* / ARUF61-00*-1* / ARUF48601A*
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 59636771596367715963677159 63 67715963677159636771
MBh 44.1 45.7 50.1 - 43.1 44.6 48.9 - 42.0 43.6 47.7 - 41.0 42.5 46.6 - 39.0 40.4 44.3 - 36.1 37.4 41.0 -
S/T 0.76 0.63 0.44 - 0.79 0.66 0.46 - 0.81 0.67 0.47 - 0.83 0.70 0.48 - 0.86 0.72 0.50 - 0.87 0.73 0.50 -
Delta T 17 15 11 - 17 15 11 - 17 15 11 - 17 15 11 - 17 15 11 - 16 14 11 -
1800 KW 3.10 3.17 3.27 - 3.34 3.41 3.52 - 3.55 3.62 3.74 - 3.73 3.81 3.93 - 3.88 3.97 4.10 - 4.02 4.11 4.24 -
AMPS 10.0 10.2 10.5 - 10.8 11.0 11.4 - 11.7 11.9 12.3 - 12.4 12.7 13.2 - 13.2 13.5 14.0 - 14.0 14.3 14.8 -
HI PR 145 156 165 - 163 175 185 - 185 199 211 - 211 227 240 - 237 256 270 - 262 282 298 -
LO PR 62 66 72 - 65 70 76 - 68 72 79 - 71 76 83 - 75 80 87 - 77 82 90 -
MBh 42.8 44.4 48.6 - 41.8 43.3 47.5 - 40.8 42.3 46.4 - 39.8 41.3 45.2 - 37.8 39.2 43.0 - 35.0 36.3 39.8 -
S/T 0.72 0.60 0.42 - 0.75 0.63 0.43 - 0.77 0.64 0.45 - 0.79 0.66 0.46 - 0.82 0.69 0.48 - 0.83 0.69 0.48 -
Delta T 18 15 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 14 11 -
70 1600 KW 3.08 3.14 3.24 - 3.31 3.38 3.49 - 3.52 3.59 3.71 - 3.70 3.78 3.90 - 3.85 3.94 4.07 - 3.99 4.07 4.21 -
AMPS 9.9 10.1 10.5 - 10.7 10.9 11.3 - 11.6 11.8 12.2 - 12.3 12.6 13.0 - 13.1 13.4 13.9 - 13.9 14.2 14.7 -
HI PR 144 155 163 - 161 174 183 - 184 197 209 - 209 225 238 - 235 253 267 - 260 280 295 -
LO PR 61 65 71 - 65 69 75 - 67 72 78 - 71 75 82 - 74 79 86 - 77 82 89 -
MBh 39.5 41.0 44.9 - 38.6 40.0 43.8 - 37.7 39.1 42.8 - 36.8 38.1 41.7 - 34.9 36.2 39.7 - 32.3 33.5 36.7 -
S/T 0.70 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.80 0.67 0.46 -
Delta T 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
1400 KW 3.01 3.07 3.16 - 3.23 3.30 3.40 - 3.43 3.51 3.62 - 3.61 3.69 3.81 - 3.76 3.84 3.97 - 3.89 3.97 4.10 -
AMPS 9.6 9.9 10.2 - 10.4 10.6 11.0 - 11.3 11.5 11.9 - 12.0 12.3 12.7 - 12.8 13.1 13.5 - 13.5 13.8 14.3 -
HI PR 139 150 159 - 157 168 178 - 178 192 202 - 203 218 230 - 228 245 259 - 252 271 286 -
LO PR 60 63 69 - 63 67 73 - 65 70 76 - 69 73 80 - 72 77 84 - 74 79 86 -
MBh 44.846.250.053.643.845.148.852.442.844.047.751.141.7
42.9
46.5 49.9 39.6 40.8 44.2 47.4 36.7 37.8 40.9 43.9
S/T 0.860.770.580.380.890.800.610.390.920.820.620.400.95
0.85
0.64 0.41 0.98 0.88 0.66 0.43 0.99 0.89 0.67 0.43
Delta T20181510201815102018151020
19
15 11 20 18 15 10 19 17 14 10
1800 KW 3.13 3.19 3.29 3.40 3.37 3.44 3.55 3.66 3.58 3.65 3.77 3.89 3.76
3.84
3.97 4.10 3.92 4.00 4.14 4.27 4.05 4.14 4.28 4.43
AMPS 10.1 10.3 10.6 11.0 10.9 11.1 11.5 11.9 11.8 12.1 12.4 12.9 12.6
12.9
13.3 13.8 13.3 13.7 14.1 14.6 14.1 14.5 14.9 15.5
HI PR 147 158 167 174 165 177 187 195 187 201 213 222 213
229
242 253 240 258 273 284 265 285 301 314
LO PR 63 67 73 77 66 70 77 82 69 73 80 85 72
77
84 89 76 81 88 94 78 83 91 97
MBh 43.544.848.552.142.543.847.450.941.542.746.349.740.5
41.7
45.1 48.4 38.5 39.6 42.9 46.0 35.6 36.7 39.7 42.6
S/T 0.820.740.560.360.850.760.580.370.870.780.590.380.90
0.81
0.61 0.39 0.94 0.84 0.63 0.41 0.94 0.84 0.64 0.41
Delta T21191611211916112119161121
19
16 11 21 19 16 11 19 18 15 10
75 1600 KW 3.10 3.17 3.27 3.37 3.34 3.41 3.52 3.63 3.55 3.62 3.74 3.86 3.73
3.81
3.94 4.07 3.89 3.97 4.10 4.24 4.02 4.11 4.25 4.39
AMPS 10.0 10.2 10.5 10.9 10.8 11.0 11.4 11.8 11.7 11.9 12.3 12.8 12.5
12.7
13.2 13.6 13.2 13.5 14.0 14.5 14.0 14.3 14.8 15.4
HI PR 145 156 165 172 163 175 185 193 185 199 211 220 211
227
240 250 238 256 270 282 262 282 298 311
LO PR 62 66 72 77 65 70 76 81 68 72 79 84 71
76
83 88 75 80 87 93 77 82 90 96
MBh 40.241.444.848.139.340.443.746.938.339.542.745.837.4
38.5
41.7 44.7 35.5 36.6 39.6 42.5 32.9 33.9 36.7 39.3
S/T 0.790.710.540.350.820.740.560.360.840.750.570.370.87
0.78
0.59 0.38 0.90 0.81 0.61 0.39 0.91 0.81 0.62 0.40
Delta T21191611212016112120161121
20
16 11 21 19 16 11 20 18 15 10
1400 KW 3.03 3.09 3.19 3.29 3.26 3.33 3.43 3.54 3.46 3.53 3.65 3.77 3.64
3.72
3.84 3.96 3.79 3.87 4.00 4.13 3.92 4.01 4.14 4.28
AMPS9.7 10.010.310.610.510.711.111.511.411.612.012.412.1
12.4
12.8 13.3 12.9 13.2 13.6 14.1 13.6 13.9 14.4 14.9
HI PR 141 152 160 167 158 170 180 187 180 194 204 213 205
220
233 243 230 248 262 273 255 274 289 302
LO PR 60 64 70 74 64 68 74 79 66 70 77 82 69
74
81 86 73 77 84 90 75 80 87 93
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves.