Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump Heat Pump User Manual


 
19
COOLING PERFORMANCE DATA
GSH130604AC
EXPANDED PERFORMANCE DATA
COOLING OPERATION
MODEL: GSH130604A* / AR*F486016B
*
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 52.3 54.2 59.4 - 51.1 52.9 58.0 - 49.8 51.7 56.6 - 48.6 50.4 55.2 - 46.2 47.9 52.5 - 42.8 44.4 48.6 -
S/T 0.70 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.80 0.67 0.46 -
Delta T 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 18 15 12 -
1800 KW 3.84 3.92 4.03 - 4.12 4.20 4.33 - 4.36 4.45 4.58 - 4.57 4.67 4.81 - 4.75 4.85 5.01 - 4.91 5.01 5.17 -
AMPS 8.1 8.2 8.5 - 8.6 8.8 9.0 - 9.2 9.4 9.7 - 9.8 10.0 10.2 - 10.3 10.5 10.8 - 10.8 11.0 11.3 -
HI PR 146 157 166 - 164 176 186 - 186 200 211 - 212 228 241 - 238 257 271 - 263 284 299 -
LO PR 59 63 68 - 62 66 72 - 65 69 75 - 68 72 79 - 71 76 83 - 74 78 85 -
MBh 52.8 54.7 60.0 - 51.6 53.5 58.6 - 50.3 52.2 57.2 - 49.1 50.9 55.8 - 46.7 48.4 53.0 - 43.2 44.8 49.1 -
S/T 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.43 - 0.77 0.65 0.45 - 0.80 0.67 0.46 - 0.81 0.68 0.47 -
Delta T 18 16 12 - 18 16 12 - 18 16 12 - 19 16 12 - 18 16 12 - 17 15 11 -
70 1883 KW 3.88 3.96 4.07 - 4.16 4.24 4.37 - 4.40 4.49 4.63 - 4.62 4.72 4.86 - 4.80 4.90 5.06 - 4.96 5.07 5.23 -
AMPS 8.2 8.3 8.5 - 8.7 8.9 9.1 - 9.3 9.5 9.8 - 9.8 10.1 10.3 - 10.4 10.6 10.9 - 10.9 11.1 11.5 -
HI PR 148 159 168 - 166 178 188 - 189 203 214 - 215 231 244 - 242 260 275 - 267 287 303 -
LO PR 60 63 69 - 63 67 73 - 65 70 76 - 69 73 80 - 72 77 84 - 75 79 87 -
MBh 52.8 54.7 60.0 - 51.6 53.5 58.6 - 50.3 52.2 57.2 - 49.1 50.9 55.8 - 46.7 48.4 53.0 - 43.2 44.8 49.1 -
S/T 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.43 - 0.77 0.65 0.45 - 0.80 0.67 0.46 - 0.81 0.68 0.47 -
Delta T 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
1900 KW 3.88 3.96 4.07 - 4.16 4.24 4.37 - 4.40 4.49 4.63 - 4.62 4.72 4.86 - 4.80 4.90 5.06 - 4.96 5.07 5.23 -
AMPS 8.2 8.3 8.5 - 8.7 8.9 9.1 - 9.3 9.5 9.8 - 9.8 10.1 10.3 - 10.4 10.6 10.9 - 10.9 11.1 11.5 -
HI PR 148 159 168 - 166 178 188 - 189 203 214 - 215 231 244 - 242 260 275 - 267 287 303 -
LO PR 60 63 69 - 63 67 73 - 65 70 76 - 69 73 80 - 72 77 84 - 75 79 87 -
MBh 53.16 54.73 59.24 63.58 51.92 53.46 57.87 62.10 50.69 52.19 56.49 60.63 49.45 50.91 55.11 59.15 46.98 48.37 52.35 56.19 43.52 44.80 48.50 52.05
S/T 0.790.710.540.350.820.740.560.360.840.750.570.370.87 0.78 0.59 0.380.900.810.610.390.910.810.620.40
Delta T22201611222016112220161122 20 17 112220161120191511
1800 KW 3.87 3.95 4.06 4.19 4.15 4.23 4.36 4.49 4.39 4.48 4.62 4.76 4.61 4.70 4.85 5.00 4.79 4.89 5.05 5.21 4.95 5.06 5.21 5.38
AMPS 8.2 8.3 8.5 8.8 8.7 8.9 9.1 9.4 9.3 9.5 9.7 10.1 9.8 10.0 10.3 10.6 10.4 10.6 10.9 11.2 10.9 11.1 11.4 11.8
HI PR 147 159 167 175 165 178 188 196 188 202 214 223 214 230 243 254 241 259 274 285 266 286 302 315
LO PR 59 63 69 74 63 67 73 78 65 69 76 81 69 73 80 85 72 76 83 89 74 79 86 92
MBh 53.7 55.3 59.8 64.2 52.4 54.0 58.4 62.7 51.2 52.7 57.1 61.2 50.0
51.4
55.7 59.7 47.5 48.9 52.9 56.8 44.0 45.3 49.0 52.6
S/T 0.800.720.540.350.830.740.560.360.850.760.580.370.88
0.79
0.60 0.38 0.91 0.82 0.62 0.40 0.92 0.82 0.62 0.40
Delta T21191611212016112120161121
20
16 11 21 19 16 11 20 18 15 10
75 1883 KW 3.91 3.99 4.10 4.23 4.19 4.27 4.40 4.54 4.44 4.53 4.67 4.81 4.66
4.75
4.90 5.06 4.84 4.94 5.10 5.26 5.00 5.11 5.27 5.44
AMPS 8.2 8.4 8.6 8.9 8.8 8.9 9.2 9.5 9.4 9.6 9.8 10.2 9.9
10.1
10.4 10.8 10.5 10.7 11.0 11.3 11.0 11.2 11.6 11.9
HI PR 149 161 170 177 167 180 190 198 190 205 216 226 217
233
247 257 244 263 277 289 270 290 306 320
LO PR 60 64 70 75 64 68 74 79 66 70 77 82 69
74
81 86 73 77 85 90 75 80 87 93
MBh 53.7 55.3 59.8 64.2 52.4 54.0 58.4 62.7 51.2 52.7 57.1 61.2 50.0 51.43 55.7 59.7 47.5 48.9 52.9 56.8 44.0 45.3 49.0 52.6
S/T 0.800.720.540.350.830.740.560.360.850.760.580.370.88 0.79 0.60 0.380.910.820.620.400.920.820.620.40
Delta T21191611211916112119161121 20 16 112119161120181510
1900 KW 3.91 3.99 4.10 4.23 4.19 4.27 4.40 4.54 4.44 4.53 4.67 4.81 4.66 4.75 4.90 5.06 4.84 4.94 5.10 5.26 5.00 5.11 5.27 5.44
AMPS 8.2 8.4 8.6 8.9 8.8 8.9 9.2 9.5 9.4 9.6 9.8 10.2 9.9 10.1 10.4 10.8 10.5 10.7 11.0 11.3 11.0 11.2 11.6 11.9
HI PR 149 161 170 177 167 180 190 198 190 205 216 226 217 233 247 257 244 263 277 289 270 290 306 320
LO PR 60 64 70 75 64 68 74 79 66 70 77 82 69 74 81 86 73 77 85 90 75 80 87 93
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves.