Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump Heat Pump User Manual


 
22
COOLING PERFORMANCE DATA
GSH130483B*
EXPANDED PERFORMANCE DATA
COOLING OPERATION
MODEL: GSH130483B* / AR*F486016B*
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 59636771596367715963677159 63 67 715963677159636771
MBh 45.0 46.0 49.2 52.6 44.0 45.0 48.0 51.3 43.0 43.9 46.9 50.1 41.9 42.8 45.7 48.9 39.8 40.7 43.5 46.5 36.9 37.7 40.3 43.0
S/T 0.86 0.80 0.65 0.49 0.89 0.83 0.68 0.51 0.91 0.86 0.70 0.52 0.94 0.88 0.72 0.54 0.98 0.92 0.75 0.56 0.98 0.92 0.75 0.56
Delta T25242117262521172625211726 25 22 172624211724232016
1400 KW 2.68 2.75 2.85 2.96 2.93 3.00 3.12 3.23 3.15 3.23 3.35 3.48 3.34 3.42 3.55 3.69 3.50 3.59 3.73 3.87 3.64 3.73 3.88 4.03
AMPS 7.4 7.6 7.8 8.0 7.9 8.1 8.3 8.6 8.5 8.7 9.0 9.3 9.1 9.3 9.6 9.9 9.6 9.8 10.1 10.5 10.1 10.3 10.7 11.0
HI PR 118 127 134 140 133 143 151 157 151 162 172 179 172 185 195 204 193 208 220 229 214 230 243 253
LO PR 60 64 70 74 63 67 74 78 66 70 76 81 69 74 80 86 72 77 84 90 75 80 87 93
MBh 48.8 49.9 53.3 57.0 47.7 48.7 52.0 55.6 46.5 47.5 50.8 54.3 45.4 46.4
49.6
53.0 43.1 44.1 47.1 50.3 40.0 40.8 43.6 46.6
S/T 0.89 0.83 0.68 0.51 0.92 0.86 0.70 0.53 0.95 0.89 0.72 0.54 0.98 0.92
0.75
0.56 1.00 0.95 0.77 0.58 1.00 0.96 0.78 0.58
Delta T25242117252421172524211725 24
21
17 25 24 21 17 23 22 20 16
80 1600 KW 2.76 2.83 2.94 3.05 3.01 3.09 3.21 3.33 3.24 3.32 3.45 3.58 3.44 3.52
3.66
3.80 3.60 3.70 3.84 3.99 3.75 3.85 3.99 4.15
AMPS 7.6 7.8 8.0 8.2 8.1 8.3 8.6 8.8 8.8 9.0 9.2 9.5 9.3 9.5
9.8
10.1 9.8 10.1 10.4 10.7 10.4 10.6 10.9 11.3
HI PR 122 131 139 145 137 147 155 162 156 167 177 184 177 191
201
210 199 215 227 236 220 237 250 261
LO PR 62 66 72 76 65 69 76 81 68 72 79 84 71 76
83
88 75 79 87 92 77 82 90 96
MBh 50.3 51.4 54.9 58.7 49.1 50.2 53.6 57.3 47.9 49.0 52.3 55.9 46.8 47.8 51.0 54.6 44.4 45.4 48.5 51.8 41.1 42.0 44.9 48.0
S/T 0.93 0.87 0.71 0.53 0.97 0.91 0.74 0.55 1.00 0.93 0.76 0.57 1.00 0.96 0.78 0.58 1.00 1.00 0.81 0.61 1.00 1.00 0.82 0.61
Delta T24232016242320162423201624 23 20 162323201621211915
1800 KW 2.79 2.86 2.96 3.08 3.04 3.12 3.24 3.36 3.27 3.35 3.48 3.61 3.47 3.56 3.69 3.84 3.64 3.73 3.87 4.02 3.79 3.88 4.03 4.19
AMPS 7.7 7.8 8.0 8.3 8.2 8.4 8.6 8.9 8.8 9.0 9.3 9.6 9.4 9.6 9.9 10.2 9.9 10.2 10.5 10.8 10.5 10.7 11.0 11.4
HI PR 123 133 140 146 138 149 157 164 157 169 179 186 179 193 203 212 201 217 229 239 223 239 253 264
LO PR 62 66 73 77 66 70 77 82 69 73 80 85 72 77 84 89 75 80 88 93 78 83 91 97
MBh 45.8 46.7 48.9 52.2 44.8 45.6 47.8 51.0 43.7 44.5 46.7 49.8 42.6 43.5 45.5 48.6 40.5 41.3 43.2 46.1 37.5 38.2 40.1 42.7
S/T 0.90 0.87 0.78 0.64 0.93 0.90 0.81 0.66 0.96 0.92 0.83 0.68 0.99 0.95 0.86 0.70 1.00 0.99 0.89 0.72 1.00 1.00 0.90 0.73
DT 27 27 25 22 27 27 25 22 27 27 26 22 28 27 26 22 27 27 25 22 25 25 24 20
1400 KW 2.71 2.78 2.88 2.99 2.96 3.03 3.15 3.27 3.18 3.26 3.38 3.51 3.37 3.46 3.59 3.72 3.53 3.62 3.76 3.91 3.68 3.77 3.91 4.06
AMPS 7.5 7.6 7.8 8.1 8.0 8.2 8.4 8.7 8.6 8.8 9.1 9.4 9.1 9.3 9.6 10.0 9.7 9.9 10.2 10.6 10.2 10.4 10.8 11.1
HI PR 119 129 136 142 134 144 152 159 152 164 173 181 174 187 197 206 195 210 222 232 216 232 245 256
LO PR 61 64 70 75 64 68 74 79 66 71 77 82 70 74 81 86 73 78 85 91 76 81 88 94
MBh 49.7 50.6 53.0 56.6 48.5 49.4 51.8 55.2 47.3 48.3 50.5 53.9 46.2 47.1 49.3 52.6 43.9 44.7 46.8 50.0 40.6 41.4 43.4 46.3
S/T 0.93 0.90 0.81 0.66 0.97 0.93 0.84 0.68 0.99 0.96 0.86 0.70 1.00 0.99 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.93 0.76
DT 27 26 25 21 27 26 25 22 27 27 25 22 27 27 25 22 25 26 25 22 23 24 23 20
85 1600 KW 2.79 2.86 2.96 3.08 3.04 3.12 3.24 3.36 3.27 3.35 3.48 3.61 3.47 3.56 3.69 3.84 3.64 3.73 3.87 4.02 3.79 3.88 4.03 4.19
AMPS 7.7 7.8 8.0 8.3 8.2 8.4 8.6 8.9 8.8 9.0 9.3 9.6 9.4 9.6 9.9 10.2 9.9 10.2 10.5 10.8 10.5 10.7 11.0 11.4
HI PR 123 133 140 146 138 149 157 164 157 169 179 186 179 193 203 212 201 217 229 239 223 239 253 264
LO PR 62 66 73 77 66 70 77 82 69 73 80 85 72 77 84 89 75 80 88 93 78 83 91 97
MBh 51.1 52.1 54.6 58.3 50.0 50.9 53.3 56.9 48.8 49.7 52.1 55.5 47.6 48.5 50.8 54.2 45.2 46.1 48.3 51.5 41.9 42.7 44.7 47.7
S/T 0.98 0.94 0.85 0.69 1.00 0.98 0.88 0.72 1.00 1.00 0.91 0.73 1.00 1.00 0.93 0.76 1.00 1.00 0.97 0.79 1.00 1.00 0.98 0.79
DT 26 25 24 21 26 25 24 21 25 25 24 21 24 25 24 21 23 24 24 21 21 22 22 19
1800 KW 2.81 2.88 2.99 3.11 3.07 3.15 3.27 3.39 3.30 3.39 3.51 3.65 3.50 3.59 3.73 3.87 3.67 3.77 3.91 4.06 3.82 3.92 4.07 4.23
AMPS 7.7 7.9 8.1 8.4 8.3 8.4 8.7 9.0 8.9 9.1 9.4 9.7 9.5 9.7 10.0 10.3 10.0 10.2 10.6 10.9 10.6 10.8 11.1 11.5
HI PR 124 134 141 147 140 150 159 165 159 171 180 188 181 195 205 214 203 219 231 241 225 242 255 266
LO PR 63 67 73 78 67 71 77 82 69 74 80 86 73 77 84 90 76 81 89 94 79 84 92 98
Shaded area is AHRI Rating Conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves.