Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump Heat Pump User Manual


 
21
COOLING PERFORMANCE DATA
GSH130483B*
EXPANDED PERFORMANCE DATA COOLING OPERATION
MODEL: GSH130483B* / AR*F486016B*
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
MBh 43.5 45.1 49.4 - 42.5 44.1 48.3 - 41.5 43.0 47.1 - 40.5 42.0 46.0 - 38.5 39.9 43.7 - 35.6 36.9 40.5 -
S/T 0.69 0.57 0.40 - 0.71 0.60 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.79 0.66 0.46 -
Delta T 20 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 18 16 12 -
1400 KW 2.63 2.70 2.80 - 2.87 2.95 3.06 - 3.09 3.16 3.28 - 3.27 3.36 3.48 - 3.43 3.52 3.65 - 3.57 3.66 3.80 -
AMPS 7.3 7.4 7.7 - 7.8 8.0 8.2 - 8.4 8.6 8.8 - 8.9 9.1 9.4 - 9.4 9.6 9.9 - 9.9 10.2 10.5 -
HI PR 116 125 132 - 130 140 148 - 148 159 168 - 168 181 191 - 190 204 215 - 209 225 238 -
LO PR 59 63 68 - 62 66 72 - 65 69 75 - 68 72 79 - 71 76 82 - 73 78 85 -
MBh 47.2 48.9 53.5 - 46.1 47.7 52.3 - 45.0 46.6 51.1 - 43.9 45.5 49.8 - 41.7 43.2 47.3 - 38.6 40.0 43.8 -
S/T 0.71 0.60 0.41 - 0.74 0.62 0.43 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.81 0.68 0.47 - 0.82 0.68 0.47 -
Delta T 19 17 13 - 20 17 13 - 20 17 13 - 20 17 13 - 19 17 13 - 18 16 12 -
70 1600 KW 2.71 2.78 2.88 - 2.96 3.03 3.15 - 3.18 3.26 3.38 - 3.37 3.46 3.59 - 3.54 3.63 3.76 - 3.68 3.77 3.92 -
AMPS 7.5 7.6 7.8 - 8.0 8.2 8.4 - 8.6 8.8 9.1 - 9.1 9.4 9.6 - 9.7 9.9 10.2 - 10.2 10.4 10.8 -
HI PR 119 129 136 - 134 144 152 - 152 164 173 - 174 187 197 - 195 210 222 - 216 232 245 -
LO PR 61 64 70 - 64 68 74 - 67 71 77 - 70 74 81 - 73 78 85 - 76 81 88 -
MBh 48.6 50.3 55.2 - 47.4 49.2 53.9 - 46.3 48.0 52.6 - 45.2 46.8 51.3 - 42.9 44.5 48.7 - 39.8 41.2 45.1 -
S/T 0.75 0.62 0.43 - 0.78 0.65 0.45 - 0.80 0.66 0.46 - 0.82 0.69 0.47 - 0.85 0.71 0.49 - 0.86 0.72 0.50 -
Delta T 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 17 15 11 -
1800 KW 2.73 2.80 2.91 - 2.99 3.06 3.18 - 3.21 3.29 3.41 - 3.40 3.49 3.62 - 3.57 3.66 3.80 - 3.71 3.81 3.95 -
AMPS 7.5 7.7 7.9 - 8.1 8.2 8.5 - 8.7 8.9 9.1 - 9.2 9.4 9.7 - 9.8 10.0 10.3 - 10.3 10.5 10.9 -
HI PR 121 130 137 - 135 146 154 - 154 166 175 - 175 189 199 - 197 212 224 - 218 235 248 -
LO PR 61 65 71 - 65 69 75 - 67 71 78 - 71 75 82 - 74 79 86 - 76 81 89 -
MBh 44.3 45.6 49.3 52.9 43.2 44.5 48.2 51.7 42.2 43.4 47.0 50.5 41.2 42.4 45.9 49.2 39.1 40.3 43.6 46.8 36.2 37.3 40.4 43.3
S/T 0.780.700.530.340.810.730.550.350.830.740.560.360.86 0.77 0.58 0.370.890.800.600.390.900.800.610.39
Delta T23211712232117122321171223 21 18 122321171221201611
1400 KW 2.66 2.72 2.83 2.93 2.90 2.97 3.09 3.20 3.12 3.19 3.32 3.44 3.31 3.39 3.52 3.65 3.47 3.56 3.69 3.83 3.61 3.70 3.84 3.99
AMPS 7.4 7.5 7.7 8.0 7.9 8.0 8.3 8.6 8.5 8.7 8.9 9.2 9.0 9.2 9.5 9.8 9.5 9.7 10.0 10.4 10.0 10.3 10.6 10.9
HI PR 117 126 133 139 131 141 149 156 149 161 170 177 170 183 193 202 191 206 218 227 212 228 240 251
LO PR 59 63 69 73 63 67 73 78 65 69 76 81 68 73 80 85 72 76 83 89 74 79 86 92
MBh 48.0 49.4 53.4 57.4 46.8 48.2 52.2 56.0 45.7 47.1 51.0 54.7 44.6
45.9
49.7 53.4 42.4 43.6 47.2 50.7 39.3 40.4 43.7 47.0
S/T 0.810.730.550.350.840.750.570.370.860.770.580.380.89
0.80
0.60 0.39 0.92 0.83 0.63 0.40 0.93 0.83 0.63 0.41
Delta T22211712232117122321171223
21
17 12 22 21 17 12 21 19 16 11
75 1600 KW 2.73 2.80 2.91 3.02 2.99 3.06 3.18 3.30 3.21 3.29 3.41 3.54 3.40
3.49
3.62 3.76 3.57 3.66 3.80 3.95 3.71 3.81 3.95 4.11
AMPS7.57.77.98.28.18.28.58.88.78.99.19.59.2
9.4
9.7 10.1 9.8 10.0 10.3 10.6 10.3 10.5 10.9 11.2
HI PR 121 130 137 143 135 146 154 161 154 166 175 183 175
189
199 208 197 212 224 234 218 235 248 258
LO PR 61 65 71 76 65 69 75 80 67 71 78 83 71
75
82 87 74 79 86 91 77 81 89 95
MBh 49.4 50.9 55.0 59.1 48.2 49.7 53.8 57.7 47.1 48.5 52.5 56.3 45.9 47.30 51.2 55.0 43.6 44.9 48.6 52.2 40.4 41.6 45.1 48.4
S/T 0.850.760.580.370.880.790.600.380.900.810.610.390.93 0.83 0.63 0.410.970.870.660.420.980.870.660.43
Delta T21201611222016112220161122 20 17 112220161120191511
1800 KW 2.76 2.83 2.94 3.05 3.01 3.09 3.21 3.33 3.24 3.32 3.45 3.58 3.44 3.52 3.66 3.80 3.60 3.70 3.84 3.98 3.75 3.85 3.99 4.15
AMPS 7.6 7.8 8.0 8.2 8.1 8.3 8.6 8.8 8.8 9.0 9.2 9.5 9.3 9.5 9.8 10.1 9.8 10.1 10.4 10.7 10.4 10.6 10.9 11.3
HI PR 122 131 139 145 137 147 155 162 156 167 177 184 177 191 201 210 199 215 227 236 220 237 250 261
LO PR 62 66 72 76 65 69 76 81 68 72 79 84 71 76 83 88 75 79 87 92 77 82 90 96
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves.