Goodman Mfg GSX Air Conditioner User Manual


 
18
COOLING PERFORMANCE DATA
GSX130361A*
EXPANDED PERFORMANCE DATA COOLING OPERATION
MODEL: GSX130361A* / CA*F4860*6** / ZP31K5E-PFV
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 596367715963677159 63 677159 63 67 715963677159636771
MBh 34.3 35.5 38.9 - 33.5 34.7 38.0 - 32.7 33.9 37.1 - 31.9 33.1 36.2 - 30.3 31.4 34.4 - 28.1 29.1 31.9 -
S/T 0.72 0.60 0.42 - 0.75 0.63 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.82 0.69 0.48 - 0.83 0.69 0.48 -
Delta T 17 15 11 - 17 15 11 - 17 15 11 - 17 15 11 - 17 15 11 - 16 14 10 -
1350 KW 2.45 2.50 2.58 - 2.63 2.69 2.77 - 2.79 2.85 2.94 - 2.94 3.00 3.09 - 3.06 3.12 3.22 - 3.16 3.23 3.33 -
AMPS 8.8 9.0 9.3 - 9.6 9.8 10.1 - 10.4 10.7 11.0 - 11.1 11.4 11.8 - 11.9 12.2 12.6 - 12.6 12.9 13.4 -
HI PR 234 252 266 - 262 282 298 - 298 321 339 - 340 366 386 - 382 411 434 - 422 454 480 -
LO PR 106 112 123 - 112 119 130 - 116 123 135 - 122 130 142 - 128 136 148 - 132 141 153 -
MBh 33.3 34.5 37.8 - 32.5 33.7 36.9 - 31.7 32.9 36.1 - 31.0 32.1 35.2 - 29.4 30.5 33.4 - 27.3 28.3 31.0 -
S/T 0.69 0.58 0.40 - 0.71 0.60 0.41 - 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.79 0.66 0.45 - 0.79 0.66 0.46 -
Delta T 18 15 12 - 18 15 12 - 18 15 12 - 18 16 12 - 18 15 12 - 17 14 11 -
70 1200 KW 2.43 2.48 2.56 - 2.61 2.67 2.75 - 2.77 2.83 2.92 - 2.91 2.97 3.07 - 3.03 3.10 3.20 - 3.13 3.20 3.31 -
AMPS 8.7 9.0 9.3 - 9.5 9.7 10.0 - 10.3 10.6 10.9 - 11.0 11.3 11.7 - 11.8 12.1 12.5 - 12.5 12.8 13.2 -
HI PR 231 249 263 - 260 279 295 - 295 318 336 - 336 362 382 - 378 407 430 - 418 450 475 -
LO PR 105 111 122 - 111 118 128 - 115 122 133 - 121 128 140 - 126 135 147 - 131 139 152 -
MBh 30.7 31.9 34.9 - 30.0 31.1 34.1 - 29.3 30.4 33.3 - 28.6 29.6 32.5 - 27.2 28.2 30.8 - 25.2 26.1 28.6 -
S/T 0.67 0.56 0.38 - 0.69 0.58 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.76 0.64 0.44 -
Delta T 18 15 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
1050 KW 2.38 2.43 2.50 - 2.55 2.61 2.69 - 2.71 2.76 2.85 - 2.84 2.90 2.99 - 2.96 3.02 3.12 - 3.06 3.12 3.22 -
AMPS 8.5 8.7 9.0 - 9.2 9.4 9.7 - 10.0 10.3 10.6 - 10.7 11.0 11.4 - 11.4 11.7 12.1 - 12.1 12.4 12.9 -
HI PR 224 242 255 - 252 271 286 - 286 308 326 - 326 351 371 - 367 395 417 - 406 436 461 -
LO PR 101 108 118 - 107 114 125 - 111 119 129 - 117 125 136 - 123 130 142 - 127 135 147 -
MBh34.935.938.941.734.135.138.040.733.3 34.2 37.139.832.4 33.4 36.2 38.8 30.8 31.7 34.4 36.9 28.6 29.4 31.8 34.2
S/T 0.820.740.560.360.850.760.580.370.87 0.78 0.590.380.90 0.81 0.61 0.39 0.94 0.84 0.63 0.41 0.94 0.84 0.64 0.41
Delta T201815102018151020 18 151020 18 15 10 20 18 15 10 18 17 14 10
1350 KW 2.47 2.52 2.60 2.68 2.66 2.71 2.79 2.88 2.82 2.88 2.97 3.06 2.96 3.02 3.12 3.22 3.08 3.15 3.25 3.36 3.19 3.26 3.36 3.47
AMPS 8.9 9.1 9.4 9.8 9.6 9.9 10.2 10.6 10.5 10.8 11.1 11.6 11.3 11.5 11.9 12.4 12.0 12.3 12.7 13.2 12.7 13.0 13.5 14.0
HI PR 236 254 268 280 265 285 301 314 301 324 342 357 343
369
390 407 386 415 439 458 427 459 485 506
LO PR 107 114 124 132 113 120 131 139 117 125 136 145 123 131 143 152 129 137 150 160 133 142 155 165
MBh33.934.937.740.533.134.136.939.632.3 33.2 36.038.631.5 32.4 35.1 37.7 29.9 30.8 33.3 35.8 27.7 28.5 30.9 33.2
S/T 0.780.700.530.340.810.730.550.350.83 0.75 0.560.360.86
0.77
0.58 0.37 0.89 0.80 0.60 0.39 0.90 0.81 0.61 0.39
Delta T201915112119161121 19 161121 19 16 11 20 19 15 11 19 18 14 10
75 1200 KW 2.45 2.50 2.58 2.66 2.63 2.69 2.77 2.86 2.79 2.85 2.94 3.04 2.94 3.00 3.09 3.20 3.06 3.12 3.22 3.33 3.16 3.23 3.33 3.44
AMPS 8.8 9.0 9.3 9.7 9.6 9.8 10.1 10.5 10.4 10.7 11.0 11.5 11.1
11.4
11.8 12.3 11.9 12.2 12.6 13.1 12.6 12.9 13.4 13.9
HI PR 234 252 266 277 262 282 298 311 298 321 339 354 340 366 386 403 382 411 434 453 422 454 480 501
LO PR 106 112 123 131 112 119 130 138 116 123 135 144 122 130 142 151 128 136 148 158 132 141 153 163
MBh31.332.234.837.430.531.434.036.529.8 30.7 33.235.629.1
29.9
32.4 34.8 27.6 28.4 30.8 33.0 25.6 26.3 28.5 30.6
S/T 0.760.680.510.330.780.700.530.340.80 0.72 0.540.350.83 0.74 0.56 0.36 0.86 0.77 0.58 0.37 0.87 0.78 0.59 0.38
Delta T211916112119161121 19 161121 19 16 11 21 19 16 11 19 18 15 10
1050 KW 2.40 2.45 2.52 2.60 2.57 2.63 2.71 2.79 2.73 2.79 2.87 2.96 2.87
2.93
3.02 3.12 2.98 3.05 3.14 3.25 3.08 3.15 3.25 3.36
AMPS 8.6 8.8 9.1 9.4 9.3 9.5 9.8 10.2 10.1 10.4 10.7 11.1 10.8 11.1 11.5 11.9 11.5 11.8 12.2 12.7 12.2 12.6 13.0 13.5
HI PR 227 244 258 269 254 274 289 302 289 311 329 343 330 355 375 391 371 399 421 439 410 441 466 486
LO PR 103 109 119 127 108 115 126 134 113 120 131 139 118 126 137 146 124 132 144 153 128 136 149 159
* Entering Indoor Dry Bulb Temperature NOTE: Shaded area is ACCA (TVA) conditions