INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
1. FLUE AND CHIMNEY REQUIREMENTS
NOTE: This appliance can only be installed in conjunction
with the flue supplied.
1.1 The flue must be sited in accordance with BS5440: Part 1
(latest editon). See diagram 1.
1.2 Any terminal which is less than 2 metres above any access
(level ground, balcony or above a flat roof to which people
have access), is to be fitted with the guard.
1.3 All vertical and horizontal flues must be securely fixed and
fire precautions followed in accordance with local and
national codes of practice.
1.4 A restrictor may be required. Refer to Technical
Specifications on previous page.
1.1 TIMBER FRAMED BUILDINGS
1.5 It will be necessary to provide additional clearance when
the fire passes through a wall containing any combustible
materials so as to prevent a fire hazard.
1.6 The hole through which the flue will pass, must have a steel
sleeve which is positioned so that an air gap of at least
25mm is maintained between the outer surface of the flue,
and any part of the sleeve.
1.7 For further guidance on the installation of gas appliances in
timber framed buildings, contact your local buildings control
authority.
NOTE: ATTENTION MUST BE GIVEN TO ALLOWING
ADEQUATE CLEARANCE AT THE SIDES AND REAR OF
THE STOVE, TO PROVIDE ACCESS FOR SERVICING.
1
AR0602