Stovax 8545LUC, P8545LUC Indoor Fireplace User Manual


 
12
2. VENTILATION
The appliance requires no additional ventilation.
3. INSTALLATION OF THE GAS SUPPLY
3.1 Before installation, ensure that the local distribution
conditions (identification of the type of gas and pressure)
and the adjustment of the appliance are compatible.
3.2 Ensure that the gas supply is capable of delivering the
required amounts of gas, and is in accordance with the rules
in force.
3.3 Soft copper tubing and soft soldered joints can be used but
must not be closer that 50mm (2") to the underside of the
firebox.
3.4 A means of isolating the gas supply to the appliance must be
provided independent of any appliance control.
3.5 All supply gas pipes must be purged of any debris that may
have entered, prior to connection to the appliance.
4. APPLIANCE LOCATION
4.1 This fire must stand on a non-combustible hearth that is at
least 12mm thick and projects 50mm minimum from the
base of the fire in all directions.
MINIMUM CLEARANCE
4.2 The fire is not suitable for installation against a combustible
wall. All combustible materials must be removed from
behind the fire.
4.3 Ensure you comply with all minimum cleaance
measurements, whether or not to combustible maerials.
INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
6
AR0604
4.4 The above dimensions provide adequate clearance at the
side and rear of the fire so that the controls can be rached
and a spillage test performed where applicable.
5. TIMBER FRAMED BUILDINGS
5.1 It will be necessary to provide additional clearance when the
fire passes through a wall containing any combustible
materials as so to prevent a fire hazard.
5.2 The hole through which the flue will pass, must have a steel
sleeve which is positioned so that an air gap of at least
25mm is maintained between the outer surface of the flue,
and any part of the sleeve.
5.3 For further guidance on the installation of gas appliances in
timber framed buildings, contact your local buildings control
authority.
NOTE: ATTENTION MUST BE GIVEN TO ALLOWING
ADEQUATE CLEARANCE AT THE SIDES AND REAR OF
THE STOVE, TO PROVIDE ACCESS FOR SERVICING.
7
AR0531
A = 954mm
B = 457mm
C = 12mm
*
* Air-space to non-combustible