FireplaceXtrordinair 44 DV XXL EF Indoor Fireplace User Manual


 
Installation (for qualified installers only) 23
Travis Industries 4050114 100-01149
Facing Requirements
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it
is considered a mantel and must meet the mantel requirements listed in this manual.
Adhesive
WARNING : Do not use adhesive to secure the cement board or facing. The high
temperatures of the fireplace may cause adhesives to emit odors. Use mastic or thin set
(or other non-combustible, non-odorous adherent) to attach the facing to the cement
board.
NOTE: Screws may be used to secure the cement board to the fireplace. Do not
penetrate the fireplace more than 3/4”
3-1/2" Min.
(both sides)
Non-combustible Facing
The fireplace requires a concrete
board (or other non-combustible)
extending from the header to the
floor and to the framing members
on both sides. Do not use
sheetrock, plywood or other
combustible.
Header
See "Face
Dimensions"
Base of
Fireplace
Keep the set-up face (shipped
on the fireplace) in place when
installing the facing.
See "Top Facing
Clearance" Below
1"
See "Face Dimensions"
Minimum Top Facing Clearance
Arch Face 14
Architectural Face
(Arts & Crafts, Art Deco, Neo-Classic,
and French Country Faces)
12