FireplaceXtrordinair 44 DV XXL EF Indoor Fireplace User Manual


 
Installation (for qualified installers only) 15
Travis Industries 4050114 100-01149
Vent Installation
In addition to the requirements below, follow the requirements provided with the vent.
Vertical Termination
(part # 1291)
Use a roof flashing and storm collar
whenever passing through the roof
Vertical Vent
Requirements
Horizontal Vent
Requirements
Minimum framing
for fire stop
Min. 1" clearance from
vertical sections to
combustible surfaces.
10"
by
10"
Use the Simpson ceiling firestop (#1263) whenever
passing through a ceiling (or enclosure and at every
floor penetration.
Combustible
Framing
Use the Travis firestop (part # 93006094) when passing
through a wall. NOTE: make sure the firestop is postitioned
correctly so the 3" clearance is allowed above the vent.
3" Min.
1" Min.
1" Min.
Combustible
Surfaces
Minimum framing
for fire stop
Minimum
12" tall
Minimum
10" wide
Slide the vent sections together and turn 1/4 turn until the sections lock in
place.
Screws are not required to secure the vent. However, three screws may be
used to secure vent sections together if desired.
High temperature sealant is recommended at the appliance starter section
connection (use high-temperature silicone or Mill-Pac®).
If disassembly is required, at time of re-assembly check to see if the vent
creates a tight fit. If it does not, apply high temperature sealant to the joints of
the affected sections.
Horizontal sections require a 1/4" rise every 12" of travel
Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)