30318 R4 9/9/2005
24
IDLE STATE
THERMOSTAT CALLS FOR HEAT
SAFETY CHECK FOR FLAME (5 SEC.)
BURNER MOTOR & IGNITOR START
SOLENOID VALVE OPENS
TRIAL FOR IGNITION
10 SEC.
BURNER FLAME MONITORED
CARRYOVER STATE
• Provides continuous spark
• LED diagnostic light ON
• Start Carr
y
over Time
r
CARRYOVER TIMER EXPIRES
RUN STATE
• I
g
niter turns off.
THERMOSTAT SATISFIED
R7184 SHUTS OFF:
• Burner Motor
• Solenoid Valve
• LED Dia
g
nostic Li
g
ht
RETURNS TO IDLE STATE
FLAME
FLA
ME
FLAME
FLAME
NO FLAME
NO FLAME
FLAME LOST
FLAME LOST
REMAINS IN IDLE STATE
R7184
SEQUENCE of
OPERATION
LOCKOUT STATE
R7184:
• Shuts off burner motor
• Shuts off igniter
• Shuts off Solenoid Valve
• Fast Flashes LED Diagnostic
Li
g
ht
TO EXIT LOCKOUT
PRESS RESET
RECYCLE TIMER STARTS
R7184:
• Shuts off Solenoid Valve
• Shuts off Igniter
• Shuts off Burner Motor
• Slow Flashes LED
dia
g
nostic li
g
ht
RECYCLE TIMER EXPIRES
(60 SECONDS
FLAME LOST
SAFETY CHECK FOR FLAME (5 SEC.)
NO FLAME
FLAME
SAFETY CHECK FOR FLAME (5 SEC.)
NO FLAME
FLAME
30 S
EC.